Panasonic WU-192ME2U9 Technical Data Manual - Page 377

Connection as a Relay Control Unit, Output terminals, Relay Circuit Examples, Alarm Display

Page 377 highlights

9 3 - 305 8 7 6 5 Connection as a Relay Control Unit The interface adaptor output terminal and input terminal specifications are given below. Use the signals most appropriate for the type of equipment being controlled. (1) Output terminals The interface adaptor provides four styles of ON (set relay) and OFF (reset relay) output signals for use by the equipment being controlled. Select the style appropriate for your application. For more information, see the "Relay Circuit Examples" section. Output style Pulse contact output ON (set) output: a-contact OFF (reset) output: a-contact Contact outputs (relay contact) 1 ON OFF Setting method S002-1: OFF S002-4: OFF S003: NO Pulse contact output ON (set) output: a-contact ON 1 OFF (reset) output: b-contact OFF S002-1: OFF S002-4: OFF S003: NC Pulse contact output ON (set) output: a-contact Both start and stop signals are sourced in turn from the ON (set) relay 1 ON Static contact output (continuous contact) OFF ON OFF OFF S002-1: OFF S002-2: OFF S002-4: ON Only the ON contact output is used. The OFF contact output becomes a local prohibit signal (see 2) S002-1: ON Only the ON contact output is used. The OFF contact output becomes a local prohibit signal (see 2) 1 The pulse width is approximately 0.5 seconds. 2 The output changes according to a signal from the central control unit. Use this signal as needed. Individual permission: OFF (continuous contact) Local prohibit: ON (continuous contact) < Contact capacity > Output ON (set) relay output (CN1, terminals 6 and 7) OFF (reset) relay output (CN1, terminals 8 and 9) Contact capacity (resistive load) 24V AC, 1 A Minimum usable load: 5 V, 100 mA 24V AC, 1 A Minimum usable load: 5 V, 100 mA Caution: Note that the ON (set) relay output and OFF (reset) relay output have different contact capacities. (2) Input terminals Status monitor signals from the equipment being controlled are received by the relay contacts. The local start/stop input uses a pulse style, so connect it to a momentary input device, such as a push switch. Input Operation answer-back input Alarm signal input Terminal numbers 1, 2 1, 3 Input style Usage No-voltage a-contact Monitor the operation (static) (start/stop condition) No-voltage a-contact Monitor general (static) alarms Thermo ON signal input 1, 4 No-voltage a-contact Monitor the load when the thermo is ON, and (static) report to the central control unit Local start/stop input 1, 5 No-voltage a-contact Equipment ON/OFF (pulse) from interface adaptor Circuit contact voltage and current: 12 V DC, 10 mA Caution: When local prohibit (central) is set by the central control unit, the local start/stop input will be ignored. When stopped, the alarm input will be ignored. Continuous contact output (no-voltage contact) Pulse contact output (no-voltage contact) (ON output a-contact + OFF output b-contact) (ON output a-contact + OFF output a-contact) Relay Circuit Examples Style Installed equipment (areas within the dashed lines are the interface adaptor) Pulse contact output (no-voltage contact) Operation circuit Operation circuit 6 8 x 1 7 ON output x 2 x 1 9 OFF output (b-contact) Common 1 x 1 x 2 Operation answer-back 2 Monitor input 6 x 1 7 ON output 8 Common 1 9 x 1 OFF output Operation x 1 (a-contact) answer-back 2 Monitor input (ON output a-contact) Operation circuit 6 7 ON output x 1 The equipment can be connected directly if it requires 24V AC, 1 A or less (inductive load). ON output 6 7 Operation circuit Equipment Input (no-voltage a-contact) COM 1 Operation 2 answer-back Alarm signal 3 Thermo ON signal 4 Local stop/start 5 input Interface adaptor 6 ON output (No-voltage a-contact) 7 COM 1 Operation answer-back 2 x 1 x 2 x 3 SW (ON/OFF) Operation contact Alarm contact Thermo ON contact Local start/stop switch Circulation fan with full heat exchanger External start / stop control input (No-voltage a-contact pulse input) Circulation fan with full heat exchanger Start / stop status output (No-voltage a-contact) Connecting to a circulation fan with a full heat exchanger Notes 1) X1, X2 are auxiliary devices. 2) The interface adaptor OFF output uses the a-contact (S003 set to NO). 3) Switch S002-1 is OFF. Switch S002-4 is OFF. 1) X1 is an auxiliary device. 2) The interface adaptor OFF output uses the b-contact (S003 set to NC). 3) Switch S002-1 is OFF. Switch S002-4 is OFF. 1) X1 is an auxiliary devices. 2) Switch S002-1 is ON. 3) The equipment can be controlled directly (power supply directly shut off) by the ON output if it requires 24V AC, 1 A or less (inductive load). 4) The output will be OFF during a commercial power outage. 5) The OFF output may be used for individual / central selection (will be ON when the central control unit is set to "central", off when the central control unit is set to "individual"). 1) X1, X2, X3 are auxiliary devices; SW is a push switch. 2) If operation answer-back from the equipment is not used, switch S002-2 is ON. In this case, the internal answer-back will be OFF during a commercial power outage. 3) If the answer-back input is unused, it should not be connected. (Only connect inputs that are used.) 1) Switch S002-1 is OFF, switch S002-2 is OFF, switch S002-4 is ON. 2) The circulation fan with full heat exchanger's external start/stop control input uses no-voltage a-contact pulse, and its start/stop condition output uses no-voltage a-contact. Caution: If the central control unit or circulation fan with full heat exchanger remote controller repeatedly and continuously initiates start/stop operations, the circulation fan with full heat exchanger may not be able to recognize the settings. 4 3 2 1 Alarm Display Item Alarm from connected equipment Alarm Meaning An alarm signal was received by the interface adaptor from a connected piece of equipment during operation. Action Investigate the reason for the alarm from the connected equipment, and remove the cause of the alarm. Service display lamps D100 D101 D102 D103 System stop The system is stopped. Not an alarm blink Off Of the items listed above, only the alarm from connected equipment is passed to an upstream central control unit, which will display "C12". If the central control unit does not have an LCD display, then its warning LED will blink. Specifications Power source 24V AC ±15% 50 / 60Hz , 1-PH Power consumption 5.7 W Operating environment 32-104 , 20-80% humidity, indoor only External dimensions 2.5"(63.8mm) (h) x 10.9"(276mm) (w) x 5.4"(136mm) (d) Weight Approx. 2.87lb.(1.3 kg) External dimensions 2.5"(63.8) 0.4"(9.2) 5.0"(126) Unit: in.(mm) 8.8"(224.0) 4.6"(116.4) 5.4"(136.0) Printed in Japan 85464369870010 DC0715-0 Control of 2WAY VRF SYSTEM 10.9"(276) 12. Interface Adaptor (CZ-CAPC2U)

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216
  • 217
  • 218
  • 219
  • 220
  • 221
  • 222
  • 223
  • 224
  • 225
  • 226
  • 227
  • 228
  • 229
  • 230
  • 231
  • 232
  • 233
  • 234
  • 235
  • 236
  • 237
  • 238
  • 239
  • 240
  • 241
  • 242
  • 243
  • 244
  • 245
  • 246
  • 247
  • 248
  • 249
  • 250
  • 251
  • 252
  • 253
  • 254
  • 255
  • 256
  • 257
  • 258
  • 259
  • 260
  • 261
  • 262
  • 263
  • 264
  • 265
  • 266
  • 267
  • 268
  • 269
  • 270
  • 271
  • 272
  • 273
  • 274
  • 275
  • 276
  • 277
  • 278
  • 279
  • 280
  • 281
  • 282
  • 283
  • 284
  • 285
  • 286
  • 287
  • 288
  • 289
  • 290
  • 291
  • 292
  • 293
  • 294
  • 295
  • 296
  • 297
  • 298
  • 299
  • 300
  • 301
  • 302
  • 303
  • 304
  • 305
  • 306
  • 307
  • 308
  • 309
  • 310
  • 311
  • 312
  • 313
  • 314
  • 315
  • 316
  • 317
  • 318
  • 319
  • 320
  • 321
  • 322
  • 323
  • 324
  • 325
  • 326
  • 327
  • 328
  • 329
  • 330
  • 331
  • 332
  • 333
  • 334
  • 335
  • 336
  • 337
  • 338
  • 339
  • 340
  • 341
  • 342
  • 343
  • 344
  • 345
  • 346
  • 347
  • 348
  • 349
  • 350
  • 351
  • 352
  • 353
  • 354
  • 355
  • 356
  • 357
  • 358
  • 359
  • 360
  • 361
  • 362
  • 363
  • 364
  • 365
  • 366
  • 367
  • 368
  • 369
  • 370
  • 371
  • 372
  • 373
  • 374
  • 375
  • 376
  • 377
  • 378
  • 379
  • 380
  • 381
  • 382
  • 383
  • 384
  • 385
  • 386
  • 387
  • 388
  • 389
  • 390
  • 391
  • 392
  • 393
  • 394
  • 395
  • 396
  • 397
  • 398
  • 399
  • 400
  • 401
  • 402
  • 403
  • 404
  • 405
  • 406
  • 407
  • 408
  • 409
  • 410
  • 411
  • 412
  • 413
  • 414
  • 415
  • 416
  • 417
  • 418
  • 419
  • 420
  • 421
  • 422
  • 423
  • 424
  • 425
  • 426
  • 427
  • 428
  • 429
  • 430
  • 431
  • 432
  • 433
  • 434
  • 435
  • 436
  • 437
  • 438
  • 439
  • 440
  • 441
  • 442
  • 443
  • 444
  • 445
  • 446
  • 447
  • 448
  • 449
  • 450
  • 451
  • 452
  • 453
  • 454
  • 455
  • 456
  • 457
  • 458
  • 459
  • 460
  • 461
  • 462
  • 463
  • 464
  • 465
  • 466
  • 467
  • 468
  • 469
  • 470
  • 471
  • 472
  • 473
  • 474
  • 475
  • 476
  • 477
  • 478
  • 479
  • 480
  • 481
  • 482
  • 483
  • 484
  • 485
  • 486
  • 487
  • 488
  • 489
  • 490
  • 491
  • 492
  • 493
  • 494
  • 495
  • 496
  • 497
  • 498
  • 499
  • 500
  • 501
  • 502
  • 503
  • 504
  • 505
  • 506
  • 507
  • 508
  • 509
  • 510

Control of 2WAY VRF SYSTEM
3
- 305
12.
Interface Adaptor (CZ-CAPC2U)
3
Printed in Japan
85464369870010
DC0715-0
Connection as a Relay Control Unit
The interface adaptor output terminal and input terminal specifications are
given below.
Use the signals most appropriate for the type of equipment being controlled.
(1) Output terminals
The interface adaptor provides four styles of ON (set relay) and OFF (reset
relay) output signals for use by the equipment being controlled.
Select the
style appropriate for your application.
For more information, see the "Relay
Circuit Examples" section.
Setting method
Contact capacity (resistive load)
Pulse contact output
ON (set) output:
a-contact
OFF (reset) output:
a-contact
Pulse contact output
ON (set) output:
a-contact
OFF (reset) output:
b-contact
Pulse contact output
ON (set) output:
a-contact
Both start and stop
signals are sourced in
turn from the ON (set)
relay
Static contact output
(continuous contact)
S002-1:
OFF
S002-4:
OFF
S003:
NO
S002-1:
OFF
S002-4:
OFF
S003:
NC
S002-1: OFF
S002-2: OFF
S002-4: ON
Only the ON contact
output is used.
The OFF contact
output becomes a
local prohibit signal
(see
2)
S002-1: ON
Only the ON contact
output is used.
The OFF contact
output becomes a
local prohibit signal
(see
2)
ON (set) relay output
(CN1, terminals 6 and 7)
OFF (reset) relay output
(CN1, terminals 8 and 9)
24V AC, 1 A
Minimum usable load: 5 V, 100 mA
24V AC, 1 A
Minimum usable load: 5 V, 100 mA
Operation
answer-back input
Alarm signal input
Thermo ON signal
input
Local start/stop
input
No-voltage a-contact
(static)
No-voltage a-contact
(static)
No-voltage a-contact
(static)
No-voltage a-contact
(pulse)
Monitor the operation
(start/stop condition)
Monitor general
alarms
Monitor the load when
the thermo is ON, and
report to the central
control unit
Equipment ON/OFF
from interface adaptor
Circuit contact voltage and current: 12 V DC, 10 mA
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
1
1
1
Output style
Contact outputs (relay contact)
Output
1 The pulse width is approximately 0.5 seconds.
2 The output changes according to a signal from the central control unit.
Use this signal as needed.
< Contact capacity >
Input
Terminal
numbers
1, 2
1, 3
1, 4
1, 5
Input style
Usage
Caution:
Note that the ON (set) relay output and OFF (reset) relay output have different
contact capacities.
(2) Input terminals
Status monitor signals from the equipment being controlled are received
by the relay contacts.
The local start/stop input uses a pulse style, so connect it to a
momentary input device, such as a push switch.
Caution:
When local prohibit (central) is set by the central control unit, the local
start/stop input will be ignored.
When stopped, the alarm input will be ignored.
Relay Circuit Examples
Style
x 1
x 2
6
7
8
9
x 1
1
2
x 1
x 1
7
6
9
8
1
2
x 1
x 1
7
6
x 1
1
2
3
4
5
x 1
x 2
x 3
SW
(ON/OFF)
6
7
1
2
x 2
6
7
Installed equipment (areas within the dashed lines are the interface adaptor)
Notes
Pulse contact output (no-voltage contact)
(ON output a-contact + OFF output a-contact)
Operation
circuit
ON output
OFF output
(b-contact)
Common
Operation
answer-back
Monitor input
1) X1, X2 are auxiliary devices.
2) The interface adaptor OFF output uses
the a-contact (S003 set to NO).
3) Switch S002-1 is OFF.
Switch S002-4 is OFF.
Pulse contact output (no-voltage contact)
(ON output a-contact + OFF output b-contact)
Operation
circuit
Operation
circuit
ON output
OFF output
(a-contact)
Common
Operation
answer-back
Monitor input
1) X1 is an auxiliary device.
2) The interface adaptor OFF output
uses the b-contact (S003 set to NC).
3) Switch S002-1 is OFF.
Switch S002-4 is OFF.
Continuous contact output (no-voltage contact)
(ON output a-contact)
ON output
Operation
circuit
ON output
The equipment can be connected directly
if it requires 24V AC, 1 A or less
(inductive load).
Equipment
1) X1 is an auxiliary devices.
2) Switch S002-1 is ON.
3) The equipment can be controlled
directly (power supply directly shut off)
by the ON output if it requires 24V AC,
1 A or less (inductive load).
4) The output will be OFF during a
commercial power outage.
5) The OFF output may be used for
individual / central selection (will be ON
when the central control unit is set to
"central", off when the central control
Input (no-voltage a-contact)
Operation
answer-back
COM
Thermo ON
signal
Alarm signal
Local
stop/start
input
Operation
contact
Alarm
contact
Thermo ON
contact
Local start/stop
switch
1) X1, X2, X3 are auxiliary devices; SW is
a push switch.
2) If operation answer-back from the
equipment is not used, switch S002-2
is ON.
In this case, the internal
answer-back will be OFF during a
commercial power outage.
3) If the answer-back input is unused, it
should not be connected.
(Only
connect inputs that are used.)
Connecting to a circulation fan
with a full heat exchanger
Interface adaptor
ON output
(No-voltage a-contact)
COM
Operation
answer-back
Circulation fan with full
heat exchanger
External start / stop
control input
(No-voltage a-contact
pulse input)
Circulation fan with full
heat exchanger
Start / stop status output
(No-voltage a-contact)
1) Switch S002-1 is OFF, switch S002-2
is OFF, switch S002-4 is ON.
2) The circulation fan with full heat
exchanger's external start/stop control
input uses no-voltage a-contact pulse,
and its start/stop condition output uses
no-voltage a-contact.
Caution:
If the central control unit or circulation fan
with full heat exchanger remote controller
repeatedly and continuously initiates
start/stop operations, the circulation fan
with full heat exchanger may not be able
to recognize the settings.
Alarm Display
Alarm
Service display
lamps
Item
Meaning
Action
D100 D101 D102 D103
Alarm from
connected
equipment
An alarm signal
was received by
the interface
adaptor from a
connected piece
of equipment
during operation.
Investigate the reason
for the alarm from the
connected equipment,
and remove the cause
of the alarm.
blink
Off
Of the items listed above, only the alarm from connected equipment is passed to an upstream
central control unit, which will display "C12".
If the central control unit does not have an LCD
display, then its warning LED will blink.
System
stop
The system is
stopped.
Not an alarm
Specifications
Power source
Power consumption
Operating environment
External dimensions
Weight
24V AC ±15%
50 / 60Hz , 1-PH
5.7 W
32-104
, 20-80% humidity, indoor only
2.5”(63.8mm) (h) x 10.9”(276mm) (w) x 5.4”(136mm) (d)
Approx. 2.87lb.(1.3 k
g
)
External dimensions
Individual permission:
Local prohibit:
OFF (continuous contact)
ON (continuous contact)
10.9”
(276)
4.6”
(116.4)
5.4”
(136.0)
8.8”
(224.0)
Unit: in.(mm)
2.5”
(63.8)
0.4”
(9.2)
5.0”
(126)
unit is set to "individual").