LiftMaster HDSL24UL Installation Manual - English - Page 56

Diagnostic Codes Table

Page 56 highlights

APPENDIX Diagnostic Codes Table Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on the display as it occurs, then disappear. LiftMaster System Installed System Informational External Entrapment Protection Inherent Entrapment Protection Code 31 34 35 36 37 38 40 41 42 43 44 45 46 47 48 50 53 54 60 61 62 63 64 65 66 Meaning Control board has experienced an internal failure. Absolute Position Encoder error, not getting position information from encoder Max-run-time exceeded error Product ID error Product ID failure Hard stop limit (Arm 1) Battery overvoltage Battery overcurrent No battery at boot up Exit loop error Shadow loop error Interrupt loop error Wireless edge battery low Motor Drive Fault Hall Sensor Fault Gate overspeed detected Brownout occurred Wireless second operator communication error Minimum number of monitored entrapment protection devices not installed. CLOSE EYE/INTERRUPT held more than 3 minutes CLOSE EDGE held more than 3 minutes OPEN EYE/EDGE held more than 3 minutes CLOSE EYE/INTERRUPT held more than 3 minutes CLOSE EYE/EDGE held more than 3 minutes OPEN EYE/EDGE held more than 3 minutes Solution Disconnect all power, wait 15 seconds, then reconnect power (reboot). If issue continues, replace main control board. Check APE assembly and wiring connections. Replace the APE assembly if necessary. Check for an obstruction, then reprogram the limits. Was the control board just replaced? If so, erase limits, enter limit setup mode and set limits. If not, disconnect all power, wait 15 seconds, then reconnect power before changing product ID harness. Unplug product ID harness then plug back in. Disconnect all power, wait 15 seconds, then reconnect power before replacing product ID harness. Limit may be set too tightly against a non-resilient hard stop (re-adjust limit). Operator may be at end of travel (re-adjust mounting). Too much voltage on the battery. Check harness. Make sure there is NOT a 24V battery on a 12V system. Possible short of the battery charge harness. Check harness. Make sure you do NOT have a 12V battery on a 24V system. Check battery connections and installation. Replace batteries if depleted to less than 20V on a 24V system or less than 10V on a 12V system. Make sure there is NOT a single 12V battery on a 24V system. Failure or missing loop (SHORT or OPEN - LiftMaster Plug-in Loop Detector only). Check loop wiring throughout connection. May be a short in the loop, or an open connection in the loop. Replace batteries in wireless edge. Check motor drive connections. Disconnect all power, wait 15 seconds, then reconnect power (reboot). If issue persists, replace motor drive. Check motor and motor drive connections. Disconnect all power, wait 15 seconds, then reconnect power (reboot). If issue persists, replace motor. Make sure the gate is installed on a level surface and not on an excessive grade. AC/DC board supply dipped below allowable level. Review power supply and wiring. If rebooting, ensure enough time for discharge of power to force a fresh boot. Check the second operator for power. If OFF, restore power and try to run the system. If powered, deactivate the wireless feature and then re-learn the second operator. Review monitored entrapment protection device connections. See page 15 for minimum requirements. Check wired input on main control board; check for alignment or obstruction. Check wired input on expansion board; check for alignment or obstruction. Saved NO YES YES YES YES NO YES YES YES YES YES YES YES YES YES YES NO YES YES 56

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60

56
Diagnostic Codes Table
Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on the display as it occurs, then disappear.
LiftMaster System
Installed System
Informational
External Entrapment
Protection
Inherent Entrapment
Protection
Code
Meaning
Solution
Saved
31
Control board has experienced an internal failure.
Disconnect all power, wait 15 seconds, then reconnect power (reboot). If
issue continues, replace main control board.
NO
34
Absolute Position Encoder error, not getting
position information from encoder
Check APE assembly and wiring connections. Replace the APE assembly
if necessary.
YES
35
Max-run-time exceeded error
Check for an obstruction, then reprogram the limits.
YES
36
Product ID error
Was the control board just replaced? If so, erase limits, enter limit setup
mode and set limits. If not, disconnect all power, wait 15 seconds, then
reconnect power before changing product ID harness.
YES
37
Product ID failure
Unplug product ID harness then plug back in. Disconnect all power, wait
15 seconds, then reconnect power before replacing product ID harness.
YES
38
Hard stop limit (Arm 1)
Limit may be set too tightly against a non-resilient hard stop (re-adjust
limit). Operator may be at end of travel (re-adjust mounting).
NO
40
Battery overvoltage
Too much voltage on the battery. Check harness. Make sure there is NOT a
24V battery on a 12V system.
YES
41
Battery overcurrent
Possible short of the battery charge harness. Check harness. Make sure
you do NOT have a 12V battery on a 24V system.
YES
42
No battery at boot up
Check battery connections and installation. Replace batteries if depleted to
less than 20V on a 24V system or less than 10V on a 12V system. Make
sure there is NOT a single 12V battery on a 24V system.
YES
43
Exit loop error
Failure or missing loop (SHORT or OPEN - LiftMaster Plug-in Loop
Detector only). Check loop wiring throughout connection. May be a short
in the loop, or an open connection in the loop.
YES
44
Shadow loop error
45
Interrupt loop error
46
Wireless edge battery low
Replace batteries in wireless edge.
YES
47
Motor Drive Fault
Check motor drive connections. Disconnect all power, wait 15 seconds,
then reconnect power (reboot). If issue persists, replace motor drive.
YES
48
Hall Sensor Fault
Check motor and motor drive connections. Disconnect all power, wait 15
seconds, then reconnect power (reboot). If issue persists, replace motor.
YES
50
Gate overspeed detected
Make sure the gate is installed on a level surface and not on an excessive
grade.
YES
53
Brownout occurred
AC/DC board supply dipped below allowable level. Review power supply
and wiring. If rebooting, ensure enough time for discharge of power to
force a fresh boot.
YES
54
Wireless second operator communication error
Check the second operator for power. If OFF, restore power and try to run
the system. If powered, deactivate the wireless feature and then re-learn
the second operator.
YES
60
Minimum number of monitored entrapment
protection devices not installed.
Review monitored entrapment protection device connections. See
page 15
for minimum requirements.
NO
61
CLOSE EYE/INTERRUPT held more than 3 minutes
Check wired input on main control board; check for alignment or
obstruction.
YES
62
CLOSE EDGE held more than 3 minutes
63
OPEN EYE/EDGE held more than 3 minutes
64
CLOSE EYE/INTERRUPT held more than 3 minutes
Check wired input on expansion board; check for alignment or
obstruction.
YES
65
CLOSE EYE/EDGE held more than 3 minutes
66
OPEN EYE/EDGE held more than 3 minutes
APPENDIX