Lantronix MatchPort b/g MatchPort b/g - User Guide - Page 49

Connect Mode, Port Numbers, Reserved for, Connect Mode Option

Page 49 highlights

5: Configuration via Serial Mode or Telnet Port the unit with this port number are received to this channel. The port number selected is the Incoming TCP/UDP port and Outgoing TCP/UDP source port. Port No (10001) ? _ The current value displays in parentheses. The default settings are 10001 for Port 1 and 10002 for Port 2. The range is 1-65535, except for the following reserved port numbers: Table 5-6. Reserved Port Numbers Port Numbers Reserved for 1 - 1024 Reserved 9999 Telnet setup 14000-14009 Reserved for Redirector 30704 Reserved (77F0h) 30718 Reserved (77FEh) Note: We recommend that you not use the reserved port numbers for this setting as incorrect operation may result. Use Port 0 for the outgoing local port to change with each connection. The port range is 50,000 to 59,999. Each subsequent connection increments the number by 1 (it wraps back around to 50,000). Only use this automatic port increment feature to initiate a connection using TCP. Set the port to a non-zero value when the unit is in a passive mode or when using UDP instead of TCP. Connect Mode Connect Mode defines the unit's connection method and its reaction to incoming connections over the network. The current value displays in parentheses. ConnectMode (C0) ? _ Enter Connect Mode options in hexadecimal notation: Note: All bit positions in the table that are blank represent "don't care" bits for that particular option, which can be set to either a 0 or 1 value. Table 5-7. Connect Mode Options Connect Mode Option a) Incoming Connection 7 6 5 4 3 2 1 0 Never accept incoming 0 0 0 Accept with active Modem Control In 0 1 0 Always Accept 1 1 0 MatchPort User Guide 49

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90

5: Configuration via Serial Mode or Telnet Port
the unit with this port number are received to this channel. The port number selected
is the Incoming TCP/UDP port and Outgoing TCP/UDP source port.
Port No (10001) ? _
The current value displays in parentheses. The default settings are 10001 for Port 1
and 10002 for Port 2. The range is 1-65535, except for the following reserved port
numbers:
Table 5-6. Reserved Port Numbers
Port Numbers
Reserved for
1 – 1024
Reserved
9999
Telnet setup
14000-14009
Reserved for Redirector
30704
Reserved (77F0h)
30718
Reserved (77FEh)
Note:
We recommend that you not use the reserved port numbers for this
setting as incorrect operation may result.
Use Port 0 for the outgoing local port to change with each connection. The port range
is 50,000 to 59,999. Each subsequent connection increments the number by 1 (it
wraps back around to 50,000).
Only use this automatic port increment feature to initiate a connection using TCP. Set
the port to a non-zero value when the unit is in a passive mode or when using UDP
instead of TCP.
Connect Mode
Connect Mode defines the unit’s connection method and its reaction to incoming
connections over the network. The current value displays in parentheses.
ConnectMode (C0) ? _
Enter Connect Mode options in hexadecimal notation:
Note:
All bit positions in the table that are blank represent “don’t care” bits for
that particular option, which can be set to either a 0 or 1 value.
Table 5-7. Connect Mode Options
Connect Mode Option
7
6
5
4
3
2
1
0
a)
Incoming Connection
Never accept incoming
0
0
0
Accept with active Modem Control In
0
1
0
Always Accept
1
1
0
MatchPort User Guide
49