Campbell Scientific AVW200 AVW200-series Vibrating Wire Interfaces - Page 46

RF401 connects to datalogger's CS I/O, ports 3 & 4 via 17855 cable

Page 46 highlights

AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules instructions are ran in a sequential mode, a different result variable should be specified for each AVW200 (see 6.1.2). The result codes are as follows: Code 0 >1 -3 Description Communication successful. Values have been written to the destination array. Number of communication failures. NAN values will be stored in the destination array. Resets to 0 upon successful communication. First communication. Values will be available on the next scan. ComPort The ComPort parameter is used to specify the communications port that will be used to communicate with the AVW200. Enter a numeric or alphanumeric code: Alphanumeric ComRS232 ComME ComSDC7 ComSDC8 ComSDC10 ComSDC11 Com1 Com2 Com3 Com4 Description AVW200 connects to datalogger's RS-232 port via 18663 cable RF401 connects to datalogger's CS I/O port; RF401 configured as modem enabled RF401 connects to datalogger's CS I/O port; RF401 configured as SDC7 RF401 connects to datalogger's CS I/O port; RF401 configured as SDC8 RF401 connects to datalogger's CS I/O port; RF401 configured as SDC10 RF401 connects to datalogger's CS I/O port; RF401 configured as SDC 11 AVW200 connects to datalogger's control ports 1 & 2 via 17855 cable AVW200 connects to datalogger's control ports 3 & 4 via 17855 cable AVW200 connects to datalogger's control ports 5 & 6 via 17855 cable AVW200 connects to datalogger's control ports 7 & 8 via 17855 cable NeighborAddr The NeighborAddr is used to specify a static route to the AVW200 (e.g., the PakBus address of a "neighbor" device that the host can go through to communicate with the AVW200). If 0 is entered, the AVW200 is assumed to be a neighbor (i.e., the host datalogger can communicate with the AVW200 directly). PakBusAddr The PakBusAddr parameter identifies the PakBus address of the AVW200 with which the host datalogger is trying to communicate. Valid entries are 1 through 4094. Each PakBus device in the network must have a unique address. Dest The Dest parameter is the variable array in which to store the results of the instruction. Dest is a single-dimensioned array of 5 or 6 (depending upon whether a thermistor is being measured) if only one sensor is being measured. Dest is a multi-dimensioned array of 5 or 6 if multiple sensors are 38

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112

AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules
instructions are ran in a sequential mode, a different result
variable should be specified for each AVW200 (see 6.1.2).
The result codes are as follows:
Code
Description
0
Communication successful.
Values have been
written to the destination array.
>1
Number of communication failures.
NAN values
will be stored in the destination array.
Resets to 0
upon successful communication.
-3
First communication. Values will be available on
the next scan.
ComPort
The ComPort parameter is used to specify the
communications port that will be used to communicate with
the AVW200.
Enter a numeric or alphanumeric code:
Alphanumeric
Description
ComRS232
AVW200 connects to datalogger’s RS-232
port via 18663 cable
ComME
RF401 connects to datalogger's CS I/O
port; RF401 configured as modem enabled
ComSDC7
RF401 connects to datalogger's CS I/O
port; RF401 configured as SDC7
ComSDC8
RF401 connects to datalogger's CS I/O
port; RF401 configured as SDC8
ComSDC10
RF401 connects to datalogger's CS I/O
port; RF401 configured as SDC10
ComSDC11
RF401 connects to datalogger's CS I/O
port; RF401 configured as SDC 11
Com1
AVW200 connects to datalogger's control
ports 1 & 2 via 17855 cable
Com2
AVW200 connects to datalogger's control
ports 3 & 4 via 17855 cable
Com3
AVW200 connects to datalogger's control
ports 5 & 6 via 17855 cable
Com4
AVW200 connects to datalogger's control
ports 7 & 8 via 17855 cable
NeighborAddr
The NeighborAddr is used to specify a static route to the
AVW200 (e.g., the PakBus address of a "neighbor" device
that the host can go through to communicate with the
AVW200). If 0 is entered, the AVW200 is assumed to be a
neighbor (i.e., the host datalogger can communicate with the
AVW200 directly).
PakBusAddr
The PakBusAddr parameter identifies the PakBus address of
the AVW200 with which the host datalogger is trying to
communicate.
Valid entries are 1 through 4094.
Each
PakBus device in the network must have a unique address.
Dest
The Dest parameter is the variable array in which to store the
results of the instruction. Dest is a single-dimensioned array
of 5 or 6 (depending upon whether a thermistor is being
measured) if only one sensor is being measured. Dest is a
multi-dimensioned array of 5 or 6 if multiple sensors are
38