LiftMaster CAPXLV Installation Manual - English French Spanish - Page 20
Door Access, Request To Exit, Supervised Door Status, Primary Relay, Auxiliary Relay, Wiegand, Door 1
View all LiftMaster CAPXLV manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 20 highlights
INTRODUCTION PRE-INSTALL INSTALL NETWORK ACCESS CONTROL Door Access Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access. Door access can be wired to Door 1, 2, 3, or 4 on the Door Boards. WIEGAND KEYPAD READER NOTE: The length of the unshielded wires should be kept to a minimum to avoid electrical noise. OR NOTE: For KPR2000 keypad, wire the pink and black (ground) wires together. 12Vdc - red GROUND - black DATA 0 - green DATA 1 - white GREEN LED - orange RED LED - brown REQUEST TO EXIT PROXIMITY PUSH SENSOR BUTTON SUPERVISED (DOOR STATUS) DOOR SENSOR (SUPERVISED) OR DOOR SENSOR (NON-SUPERVISED) EOL (End of Line) Resistor (1k ohm) *PRIMARY RELAY DOOR STRIKE For AC Power: Install a Siemens S10K30MOV (Metal Oxide Varistor) (provided) or equivalent Power for Door Strike (Not Provided) Use 18-22 AWG COMMON + OR REQUEST TO EXIT GROUND SUPERVISED NORMALLY OPEN COMMON NORMALLY CLOSED NORMALLY OPEN COMMON - - NORMALLY OPEN For DC Power: Install a 1N4005 diode or equivalent OR MAGLOCK For AC Power: Install a Siemens S10K30MOV (Metal Oxide Varistor) (provided) or equivalent Use 18-22 AWG NORMALLY CLOSED For DC Power: Install a 1N4005 diode or equivalent COMMON + Power for Maglock (Not Provided) DO NOT use the power supply for the controller AUXILIARY RELAY Low Voltage Power Supply LIGHT NEUTRAL Isolation Relay LOAD LINE NOTE: DO NOT run high voltage power within OR the CAPXL enclosure. ALARM BYPASS COMMON NORMALLY OPEN 20 DOOR 1, 2, 3, or 4 * NOTE: MAGLOCK, door strike and ALARM BYPASS not evaluated by UL.