Panasonic WU-216MF2U9 - Service Manual - Page 56

Detailed Settings in EEPROM of Outdoor Unit, Display P 1=non-displayed

Page 56 highlights

14. Detailed Settings in EEPROM of Outdoor Unit 3WAY VRF SYSTEM Control Functions Never use the DN code unlisted in the following table. (P) : Factory preset mode DN Item Setting No. 04 Operation for using snowfall sensor 0=No sensor & control (P) 1=Sensor & control 2=No Sensor & no control 3=Sensor & no control 0=Invalid (P) 05 Outdoor fan silent mode 1=Silent mode 1 2=Silent mode 2 ,,,,, 12=Silent mode 12 0=Invalid 1=stop for 2 hours and drive for 20 min. constantly 0C Indoor unit drain pump forced operation 2=stop for 20 min. and drive for 20 min. constantly 3=Drive constantly 1 4-6=delay drive when thermostat OFF 7=delay drive when thermostat OFF (P) 0D Measures against smell when indoor unit cooling thermostat OFF 0=Invalid (P) 1=Measures against smell 1A Demand 1 current (%) 2 1B Demand 2 current (%) 0=0% ,,,,,40=40% ,,,,,45=45% ,,,,,100=100% (P) ,,,,,140=140% -1=No control 0=0% ,,,,,40=40% ,,,,,70=70% (P) ,,,,,100=100% ,,,,,140=140% -1=No control 0=No display 1E Demand remote controller display 1=When demand control active, "demand - actived" displayed (P) 2=When forced thermostat OFF with demand control active, 3 23 E06 ignore function "demand - actived" displayed -1=invalid (P),,,,, 0=0,,,,, 1=1,,,,, 13=13 14-52=Never use 2A Dew condensation prevention control of indoor unit 0=Invalid (P) 1=30 min, 2=40 min, 3=50 min, 4=60 min 4 2B DP operation time for slime measures 20=20 min, 30=30 min (P), 40=40 min 50=50 min, 60=60 min 0=8 sec delay-start (P) 3E PSccutgt delay-start setting 1=(system address ×1×8) sec delay-start 2=(system address ×2×8) sec delay-start 3=(system address ×3×8) sec delay-start 5 Indoor unit fan's intermittent operation 44 and operating time when in cooling 30=30 sec , 60=60 sec (P) ,,,,, 240=240 sec thermostat OFF 6 Indoor unit fan's intermittent operation 45 and stopped time when in cooling thermostat OFF 49 Automatic backup mode setting 5=5 min (P) , 10=10 min , 15=15 min , 20=20 min , 25=25 min 30=30 min 0=Display (P) 1=non-displayed 81 Outdoor unit capacity 7 0=Invalid , 1=22 , 2=25 , 3=28 , 4=32 , 5=36 , 6=40 , 7=45 , 8=50 , 9=56 , 10=63 , 11=71 , 12=80 , 13=90 , 14=100 , 15=112 , 16=125 , 17=140 , 18=160 , 19=180 , 20=210 , 21=224 , 22=250 , 23=280 , 24=335 , 25=355 , 26=420 , 27=450 , 28=500 , 29=560 , 30=600 , 31=630 , 32=670 , 33=710 , 34=800 , 35=840 8F High static pressure setting 0=Invalid (P) 1=High static pressure mode 2-6=Never use 8 A3 The minimum operating time 1 until defrosting 20=20min, 21=21min ,,,,, 40=40min (P) 41 - 90=Never use A7 Validity/invalidity of capacity control when cooling operation 0=Invalid (P), 1=Valid 9 1 - 48

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211

3WAY VRF SYSTEM
Control Functions
1
- 48
1
14. Detailed Settings in EEPROM of Outdoor Unit
Never use the DN code unlisted in the following table.
(P) : Factory preset mode
DN
Item
Setting No.
04
Operation for using snowfall sensor
0=No sensor & control (P)
1=Sensor & control
2=No Sensor & no control
3=Sensor & no control
05
Outdoor fan silent mode
0=Invalid (P)
1=Silent mode 1
2=Silent mode 2 ,,,,, 12=Silent mode 12
0C
Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 min. constantly
2=stop for 20 min. and drive for 20 min. constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
0D
Measures against smell when indoor
unit cooling thermostat OFF
0=Invalid (P)
1=Measures against smell
1A
Demand 1 current (%)
0=0% ,,,,,40=40% ,,,,,45=45% ,,,,,100=100% (P) ,,,,,140=140%
-1=No control
1B
Demand 2 current (%)
0=0% ,,,,,40=40% ,,,,,70=70% (P) ,,,,,100=100% ,,,,,140=140%
-1=No control
1E
Demand remote controller display
0=No display
1=When demand control active, “demand - actived” displayed (P)
2=When forced thermostat OFF with demand control active,
“demand - actived” displayed
23
E06 ignore function
-1=invalid (P),,,,, 0=0,,,,, 1=1,,,,, 13=13
14-52=Never use
2A
Dew condensation prevention control of
indoor unit
0=Invalid (P)
1=30 min, 2=40 min, 3=50 min, 4=60 min
2B
DP operation time for slime measures
20=20 min, 30=30 min (P), 40=40 min
50=50 min, 60=60 min
3E
PSccutgt delay-start setting
0=8 sec delay-start (P)
1=(system address ×1×8) sec delay-start
2=(system address ×2×8) sec delay-start
3=(system address ×3×8) sec delay-start
44
Indoor unit fan's intermittent operation
and operating time when in cooling
thermostat OFF
30=30 sec , 60=60 sec (P) ,,,,, 240=240 sec
45
Indoor unit fan's intermittent operation
and stopped time when in cooling
thermostat OFF
5=5 min (P) , 10=10 min , 15=15 min , 20=20 min , 25=25 min
30=30 min
49
Automatic backup mode setting
0=Display (P) 1=non-displayed
81
Outdoor unit capacity
0=Invalid , 1=22 , 2=25 , 3=28 , 4=32 , 5=36 , 6=40 , 7=45 ,
8=50 , 9=56 , 10=63 , 11=71 , 12=80 , 13=90 , 14=100 ,
15=112 , 16=125 , 17=140 , 18=160 , 19=180 , 20=210 ,
21=224 , 22=250 , 23=280 , 24=335 , 25=355 , 26=420 ,
27=450 , 28=500 , 29=560 , 30=600 , 31=630 , 32=670 ,
33=710 , 34=800 , 35=840
8F
High static pressure setting
0=Invalid (P)
1=High static pressure mode
2-6=Never use
A3
The minimum operating time 1 until
defrosting
20=20min, 21=21min ,,,,, 40=40min (P)
41 - 90=Never use
A7
Validity/invalidity of capacity control
when cooling operation
0=Invalid (P), 1=Valid