Panasonic WU-216MF2U9 - Service Manual - Page 137
Operating the High-spec Wired Remote, Controller CZ-RTC5A, How to set the external static pressure
View all Panasonic WU-216MF2U9 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 137 highlights
2. Detailed Settings Function 3WAY VRF SYSTEM Remote Controller Functions 1-2. Operating the High-spec Wired Remote Controller (CZ-RTC5A) Detailed settings 20:30 (THU) Unit no. Code no. Set data 3-1 B0 0001 20:30 (THU) Sel. Next 4. Select the "Set data" by pressing the or button. [ ] START Select one of the "Set data" among "0001" - "0015" according to the desired external static pressure setting by pressing the or button. Then press the button. (See the table below.) 1 When setting to auto airflow volume control: Select the setting data to "-002". How to set the external static pressure Then press the button. 1. Keep pressing the , and buttons simultaneously for 4 or more seconds. The "Maintenance func" screen appears on the LCD display. Indoor unit Item code 2 7, 9, 12, 15, 18, 24 36, 48, 54 External static pressure of the rated air B0 Maintenance func 20:30 (THU) flow volume 1. Outdoor unit error data 2. Service contact 3. RC setting mode 4.Test run Sel. Page [ ] Confirm 0.60 in.WC (150 Pa) 0.56 in.WC (140 Pa) 0.60 in.WC (150 Pa) 0.56 in.WC (140 Pa) 0015 0014 3 0.52 in.WC (130 Pa) 0.52 in.WC (130 Pa) 0013 0.48 in.WC (120 Pa) 0.48 in.WC (120 Pa) 0012 2. Press the or button to see each menu. If you wish to see the next screen instantly, press the or button. 0.40 in.WC (100 Pa) 0.44 in.WC (110 Pa) 0011 0.28 in.WC (70 Pa) 0.40 in.WC (100 Pa) 0008 4 0.24 in.WC (60 Pa) 0.28 in.WC (70 Pa) 0006 Select "8. Detailed settings" on the LCD display 0.20 in.WC (50 Pa) 0.20 in.WC (50 Pa) 0005 and press the button. 0.12 in.WC (30 Pa) 0.12 in.WC (30 Pa) 0003 0.04 in.WC (10 Pa) 0.04 in.WC (10 Pa) 0001 Maintenance func 20:30 (THU) No auto airflow volume setting -001 5 5. Sensor info. 6. Servicing check Auto airflow volume setting -002 7. Simple settings 8. Detailed settings 5. Select the "Unit no." by pressing the or Sel. Page [ ] Confirm button and press the button. The "Detailed settings" screen appears on the LCD The "Exit detailed settings and restart?" (Detailed 6 display. setting-end) screen appears on the LCD display. Select the "Unit no." by pressing the or Select "YES" and press the button. button for changes. When the setting is completed, perform the Detailed settings 20:30 (THU) Unit no. Code no. Set data test run for the external static pressure setting described in "Auto External Static Pressure Setting 7 Operation". 3-1 B0 0001 Sel. Next 3. Select the "Code no." by pressing the or button. Change the "Code no." to "B0" by pressing the Detailed settings 20:30 (THU) Unit noE.xit adneCdtaoriledesedtasnreot?t.tings Set data 1-1 10 0001 8 YES NO Sel. Next or button (or keeping it pressed). 4 - 19 9