LiftMaster CAPXM Installation Manual - English French Spanish Manufactured Pri - Page 15

Connect Power, Wire Specification, Maximum Run Distance

Page 15 highlights

INTRODUCTION PRE-INSTALL INSTALL NETWORK ACCESS CONTROL 4 Connect Power INTRODTUhCe TouIOtleNt for the CPAPRXEM-IMNUSSTTAbLeLan external dedINicaSteTdA1L2L0 Vac outlet. NET•W DOORNKOT use ANAYCpCowEeSr SsuCppOlyNoTthRerOL Refer to the table below for maximum wire run distances. This outlet should than those supplied with your CAPXM. be wired back to its own 10 Amp minimum circuit breaker. • DO NOT power electronic strikes and latches with the same power supply WIRE SPECIFICATION 14 AWG MAXIMUM RUN DISTANCE Up to 300 feet (91.4 m) used to power the access control panel; doing so will cause DAMAGE to the CAPXM. Use ONLY a UL listed burglar INTRODUCTION 16 APWRGE-INSTALL Up toIN2S00TAfeLetL(60.9 m) NETWaplOoawrRmeKroerleacctcroesnsicAcsCotnrCitkrEeosSl saSynsdCtelOmatNcthoTeRs.OL 18 AWG Up to 100 feet (30.4 m) • DO NOT connect the power supply to a switched outlet or otherwise controlled 1. Connect 14-18 AWG wire to the stripped secondary DC output wires on the power supply. Black is negative and red is positive. AC outlet. • DO NOT connect the power supply to the 120 Vac outlet until ALL wiring is 2. Remove the PWR INPUT terminal block from the Control Board. completed. • Install the transient noise suppression 3. Connect the power supply wires to the PWR INPUT terminal block (red device (MOV) supplied with the CAPXM to +24V and black to GND). Reattach the terminal block to the Control for AC powered devices and Diode for Board. DC powered devices. 4. Plug the power supply into a 120 Vac outlet after all connections have been made. • DISCONNECT the power supply from the 120 Vac outlet prior to removing or attaching the terminal block to the  NOTE: The green LED on the door board will blink and the green Control Board. LEDs on the Control Board will light solid when powered up. The CAPXM will display the LiftMaster logo while booting up. When boot up is complete, the user interface will appear. 5. Close the CAPXM door. POWER INPUT Control Board Dedicated 10 Amp Minimum Circuit NOTE: If the power supply is installed outdoors, the power supply must have its own approved NEMA 4 Rated weatherproof electrical enclosure. Use conduit from the power supply enclosure to the controller enclosure. Power Supply 15 120 Vac Dedicated Outlet

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80

15
Connect Power
4
DO NOT use ANY power supply other
than those supplied with your CAPXM.
DO NOT power electronic strikes and
latches with the same power supply
used to power the access control panel;
doing so will cause DAMAGE to the
CAPXM. Use ONLY a UL listed burglar
alarm or access control system to
power electronic strikes and latches.
DO NOT connect the power supply to a
switched outlet or otherwise controlled
AC outlet.
DO NOT connect the power supply to
the 120 Vac outlet until ALL wiring is
completed.
Install the transient noise suppression
device (MOV) supplied with the CAPXM
for AC powered devices and Diode for
DC powered devices.
DISCONNECT the power supply from
the 120 Vac outlet prior to removing or
attaching the terminal block to the
Control Board.
The outlet for the CAPXM MUST be an external dedicated 120 Vac outlet.
Refer to the table below for maximum wire run distances. This outlet should
be wired back to its own 10 Amp minimum circuit breaker.
1.
Connect 14-18 AWG wire to the stripped secondary DC output wires on
the power supply. Black is negative and red is positive.
2.
Remove the PWR INPUT terminal block from the Control Board.
3.
Connect the power supply wires to the PWR INPUT terminal block (red
to +24V and black to GND). Reattach the terminal block to the Control
Board.
4.
Plug the power supply into a 120 Vac outlet after all connections have
been made.
NOTE:
The green LED on the door board will blink and the green
LEDs on the Control Board will light solid when powered up. The
CAPXM will display the LiftMaster logo while booting up. When
boot up is complete, the user interface will appear.
5.
Close the CAPXM door.
INTRODUCTION
PRE-INSTALL
NETWORK
INSTALL
ACCESS CONTROL
Dedicated 10 Amp Minimum Circuit
120 Vac
Dedicated Outlet
Power Supply
POWER INPUT
Control Board
NOTE: If the power supply is installed
outdoors, the power supply must have
its own approved NEMA 4 Rated
weatherproof electrical enclosure.
Use conduit from the power supply
enclosure to the controller enclosure.
WIRE SPECIFICATION
MAXIMUM RUN DISTANCE
14 AWG
Up to 300 feet (91.4 m)
16 AWG
Up to 200 feet (60.9 m)
18 AWG
Up to 100 feet (30.4 m)