MODEL LA412U SYMPTOM: Operator does not have power. POWER CONTROL BOX CONTROL BOARD * 3 Check the control board.* Try replacing the fuse. If that does not work, replace the control board. CONTROL BOARD J15 Plug 20A Diode 1 Check the solar panels.* Check the voltage coming from the solar panels (red and black wires on the J15 plug labeled "DC POWER"). Check the voltage when the panel is in full sun. The voltage should be 12 Vdc (+/- 10%). If not, refer to the Solar Troubleshooting section. Solar Panels 10W minimum - 30W maximum, wired in parallel Battery 12V 7AH Battery 12V 7AH Red Black Black 10W 12V 2 Check the batteries.* Red Check the battery connections. Make sure there is one 7AH battery, two 7AH batteries wired in paralllel, OR one 33AH battery connected. Check the voltage coming from each battery by disconnecting the battery from the operator. A fully charged battery should read 12.8 to 13.3 Vdc per battery. If not, replace the batteries. 10W 12V 10W 12V 22

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

22
POWER
Diode
20A
Battery
12V 7AH
Battery
12V 7AH
Solar Panels
10W minimum - 30W maximum, wired in parallel
10W 12V
10W 12V
20A
10W 12V
J15 Plug
Black
Red
Black
Red
CONTROL BOX
1
Check the solar panels.*
Check the voltage coming from
the solar panels (red and black
wires on the J15 plug labeled
“DC POWER”). Check the voltage
when the panel is in full sun.
The voltage should be
12 Vdc (+/- 10%).
If not, refer to the Solar
Troubleshooting section.
2
Check the batteries.*
Check the battery connections. Make sure there is one 7AH battery,
two 7AH batteries wired in paralllel, OR one 33AH battery connected.
Check the voltage coming from each battery by disconnecting the battery
from the operator. A fully charged battery should read 12.8 to 13.3 Vdc per
battery. If not, replace the batteries.
3
Check the control board.*
Try replacing the fuse.
If that does not work, replace
the control board.
*
CONTROL BOARD
CONTROL BOARD
MODEL LA412U
SYMPTOM: Operator does not have power.