DIAGNOSTIC CODES Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on the display as it occurs, then disappear. When servicing of the operator is complete, erase the code history by pressing the STOP button until the display flashes "Er" then "CL" (about 6 seconds). When the codes have been erased the display will show "_ _". LIFTMASTER SYSTEM EXTERNAL ENTRAPMENT PROTECTION Code 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 Meaning System AC Overvoltage System AC Undervoltage Limit Error - Stuck Switch Symptom Operator will not function and show code 55. Operator will continue to run and show code 56. Operator will not run and show code 57. Limit Error - Wrong Switch Missing Power Board Operator will not run and show code 58. Operator will not run and show code 59. Minimum number of monitored entrapment protection devices (one) not installed. The operator will not run and the EYES EDGE LEDs will flash on the main board and expansion board. CLOSE EYE/INTERRUPT held The operator will only move with more than 3 minutes on main constant pressure and will beep while board moving CLOSE EDGE held more than 3 minutes on main board OPEN EYE/EDGE held more than 3 minutes on main board CLOSE EYE/INTERRUPT held The operator will only move with more than 3 minutes on constant pressure and will beep while expansion board moving CLOSE EYE/EDGE held more than 3 minutes on expansion board OPEN EYE/EDGE held more than 3 minutes on expansion board Wireless edge triggered more Gate will not move. than 3 minutes Wireless edge loss of monitoring Gate will not move. Wireless edge triggered Gate reverses to the opposite direction. Solution Check with the utility company. Check wiring and wire gauge to operator. Check switch for proper operation. Check harness for shorts. Replace if defective. Check motor wiring. Check harness for shorts. Check for presence of power board. Make sure there is a monitored entrapment protection device installed and connected to the operator. Check for alignment or obstruction. Check wired input on main control board. The photoelectric sensors may be installed too far apart. Check for alignment or obstruction. Check wired input on expansion board. The photoelectric sensors may be installed too far apart. Check wired input for wiring issue, obstruction or damaged edge. Check wireless edge inputs. Confirm the transmitter and receiver are installed at the recommended locations and within the range specified. Confirm the transmitter battery is operational and installed securely. Check the receiver to main control board wiring harness for damage and make sure the connector is fully seated. If an obstruction occurred, no action required. If an obstruction did NOT occur, check inputs and wiring. Saved YES YES YES YES YES NO YES YES YES YES NO 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

13
Code
Meaning
Symptom
Solution
Saved
LIFTMASTER SYSTEM
55
System AC Overvoltage
Operator will not function and show
code 55.
Check with the utility company.
YES
56
System AC Undervoltage
Operator will continue to run and show
code 56.
Check wiring and wire gauge to operator.
YES
57
Limit Error - Stuck Switch
Operator will not run and show code 57.
Check switch for proper operation. Check
harness for shorts. Replace if defective.
YES
58
Limit Error - Wrong Switch
Operator will not run and show code 58.
Check motor wiring.
YES
59
Missing Power Board
Operator will not run and show code 59.
Check harness for shorts. Check for presence of
power board.
YES
EXTERNAL ENTRAPMENT PROTECTION
60
Minimum number of
monitored entrapment
protection devices (one) not
installed.
The operator will not run and the EYES
EDGE LEDs will flash on the main board
and expansion board.
Make sure there is a monitored entrapment
protection device installed and connected to the
operator.
NO
61
CLOSE EYE/INTERRUPT held
more than 3 minutes on main
board
The operator will only move with
constant pressure and will beep while
moving
Check for alignment or obstruction. Check wired
input on main control board. The photoelectric
sensors may be installed too far apart.
YES
62
CLOSE EDGE held more than
3 minutes on main board
63
OPEN EYE/EDGE held more
than 3 minutes on main board
64
CLOSE EYE/INTERRUPT held
more than 3 minutes on
expansion board
The operator will only move with
constant pressure and will beep while
moving
Check for alignment or obstruction. Check wired
input on expansion board. The photoelectric
sensors may be installed too far apart.
YES
65
CLOSE EYE/EDGE held more
than 3 minutes on expansion
board
66
OPEN EYE/EDGE held more
than 3 minutes on expansion
board
67
Wireless edge triggered more
than 3 minutes
Gate will not move.
Check wired input for wiring issue, obstruction
or damaged edge.
YES
68
Wireless edge loss of
monitoring
Gate will not move.
Check wireless edge inputs. Confirm the
transmitter and receiver are installed at the
recommended locations and within the range
specified. Confirm the transmitter battery is
operational and installed securely. Check the
receiver to main control board wiring harness for
damage and make sure the connector is fully
seated.
YES
69
Wireless edge triggered
Gate reverses to the opposite direction.
If an obstruction occurred, no action required. If
an obstruction did NOT occur, check inputs and
wiring.
NO
DIAGNOSTIC CODES
Some codes are saved in the code history and some are not. If a code is not saved it will briefly appear on the display as it occurs, then disappear.
When servicing of the operator is complete, erase the code history by pressing the STOP button until the display flashes “Er” then “CL” (about 6
seconds). When the codes have been erased the display will show “_ _”.