HP Latex R2000 Site Preparation Guide - Page 13
Configuration 4: 200–240 V line-to-line three-phase configuration with single- phase control
![]() |
View all HP Latex R2000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
AC Power cable specifications Configuration Wire Terminals External diameter range Three-phase line Single-phase line 5 wires, L1/L2/L3/N/PE 3 wires, L/N/PE Strained Cu minimum, 10 mm² or 8 AWG Strained Cu minimum, 1.5 mm² or 16 AWG Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal 22.0-33.0 mm 5.0-11.0 mm Configuration 4: 200-240 V line-to-line three-phase configuration with single- phase control Specifications Three-phase line Single-phase control Number of power wires Input voltage (line to line) 4 (L1/L2/L3/PE) 200-240 V (±10%) 3 (L/N/PE) 100-240 V (±10%) Input frequency 50/60 Hz 50/60 Hz Maximum load current (per phase) 56 A 10 A Branch circuit breaker specifications Three-phase Two-phase control 3 poles, 63/70 A 2 poles, 15/16/20 A AC Power cable specifications Configuration Wire Terminals External diameter range Three-phase line Single-phase line 4 wires, L1/L2/L3/PE 3 wires, L/N/PE Strained Cu minimum, 10 mm² or 8 AWG Strained Cu minimum, 2.5 mm² or 16 AWG Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal 22.0-33.0 mm 5.0-11.0 mm ENWW System operation requirements 9