HP Latex R2000 Site Preparation Guide - Page 12

Configuration 2: 200–240 V line-to-line three-phase configuration

Page 12 highlights

Configuration 2: 200-240 V line-to-line three-phase configuration Three-phase specifications Number of power wires) Input voltage (line to line) Input frequency 4 (L1/L2/L3/PE) 200-240V (±10%) 50/60 Hz Maximum load current (per phase) 56 A Branch circuit breaker specifications Three-phase 3 poles, 63/70 A AC three-phase power cable specifications Configuration 4 wires, L1/L2/L3/PE Wire Strained Cu minimum, 10 mm² or 6 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal External diameter range 22.0-33.0 mm Configuration 3: 380-415 V line-to-line three-phase configuration with single- phase control Specifications Three-phase line Single-phase control Number of power wires 5 (L1/L2/L3/N/PE) 3 (L/N/PE) Input voltage (line to line) 380-415 V~ (-10%) 100-240 V (±10%) Input frequency 50/60 Hz 50/60 Hz Maximum load current (per phase) 35 A 10 A Branch circuit breaker specifications Three-phase Two-phase control 4 poles,40/50 A 2 poles, 15/16/20 A 8 Chapter 2 Site preparation ENWW

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Configuration 2: 200–240 V line-to-line three-phase configuration
Three-phase specifications
Number of power wires)
4 (L1/L2/L3/PE)
Input voltage (line to line)
200–240V (±10%)
Input frequency
50/60 Hz
Maximum load current (per phase)
56 A
Branch circuit breaker specifications
Three-phase
3 poles, 63/70 A
AC three-phase power cable specifications
Configuration
4 wires, L1/L2/L3/PE
Wire
Strained Cu minimum, 10 mm² or 6 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
External diameter range
22.0–33.0 mm
Configuration 3: 380–415 V line-to-line three-phase configuration with single- phase control
Specifications
Three-phase line
Single-phase control
Number of power wires
5 (L1/L2/L3/N/PE)
3 (L/N/PE)
Input voltage (line to line)
380–415 V~ (–10%)
100–240 V (±10%)
Input frequency
50/60 Hz
50/60 Hz
Maximum load current (per phase)
35 A
10 A
Branch circuit breaker specifications
Three-phase
4 poles,40/50 A
Two-phase control
2 poles, 15/16/20 A
8
Chapter 2
Site preparation
ENWW