Gas Pressure Regulator The gas pressure regulator supplied with this range must be used. For proper operation, the inlet pressure to the regulator should be as follows. Natural Gas LP Gas Minimum Pressure 5" WCP (Water Column Pressure) Minimum Pressure 11" WCP (Water Column Pressure) Maximum Pressure 14" WCP (Water Column Pressure) Maximum Pressure 14" WCP (Water Column Pressure) note: Contact your local gas supplier if you are not sure about the inlet pressure. Gas Supply Pressure Testing note: Gas supply pressure for testing regulator must be at least 1" WCP (Water Column Pressure) above the manifold pressure shown of the model/serial rating plate. • Line pressure testing above 0.5 psi gauge (14" WCP): The range and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system test pressures in excess of 0.5 psi (3.5kPa). • Line pressures testing at 0.5 psi gauge (14"WCP) or lower: The range must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 0.5 psi (3.5kPa). 10

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40

10
Gas Pressure Regulator
The gas pressure regulator supplied with this range must be used� For proper operation, the inlet pressure to the
regulator SHOULD BE as follows�
Natural Gas
LP Gas
Minimum Pressure
5” WCP (Water Column Pressure)
Minimum Pressure
11” WCP (Water Column Pressure)
Maximum Pressure
14” WCP (Water Column Pressure)
Maximum Pressure
14” WCP (Water Column Pressure)
NOTE
:
Contact your local gas supplier if you are not sure about the inlet pressure�
Gas Supply Pressure Testing
NOTE
:
Gas supply pressure for testing regulator MUST BE at least 1” WCP (Water Column Pressure) above the
manifold pressure shown of the model/serial rating plate�
Line pressure testing above 0�5 psi gauge (14” WCP): The range and its individual shut-off valve must be
disconnected from the gas supply piping system during any pressure testing of that system test pressures in
excess of 0�5 psi (3�5kPa)�
Line pressures testing at 0�5 psi gauge (14”WCP) or lower: The range must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 0�5 psi (3�5kPa)�