TROUBLESHOOTING WARNING - DISCONNECT BATTERIES AND AC POWER BEFORE SERVICING ANY MECHANICAL OR MOVING COMPONENTS. BATTERY CHECKOUT When the batteries become weak the gate will begin to run noticeably slower. NOTE: Batteries should only be checked when you are sure they have had adequate time to fully charge. 1. Turn off the AC power and run gate for 5 to 10 cycles while observing low battery indicator LED D12. If LED 12 comes ON, batteries are too weak to function properly. If LED 12 does not light, then voltage should be checked as they still maybe near failure. Correct voltage is approximately 24.5 Vdc. NOTE: If LED D12 does light, gate will open to conserve batteries in this test or in a real power loss, even if mode switch 8 on S2 is off. Return of AC power will clear low battery indicator. Correct charge voltage is 27.5 Vdc with batteries not connected (set with R63, shown on the Control Board Layout page). GATE NOT OPERATING GATE WILL NOT OPERATE. Is the HBEAT flashing? Yes Is the "BAT LO" LED on? No No Check the battery connections. Yes Is the HBEAT flashing now? No Is S2-8 (open on AC fail) on? Yes No Is the AC PWR LED on? Is the shadow input active? Yes No Is the Safety, Back away, or Open input active? Yes No Yes Clear the active input to allow the gate to open. Clear the active input to allow the gate to close. Check fuse F4 Replace if blown. Restore AC power No and/or turn AC power switch ON. Is the AC power LED on now? No Check fuse F3, Replace if blown. Yes Allow operator to charge before operation. Does the IRD light while operating? Yes No Is the IRD flashing? Yes Make sure the gate is not binding, then adjust the IRD. Verify the gate reverses when obstructed. The max timer (MRT) has expired. Remove AC and battery power then reapply to reset. Inspect the belt for slippage and verify the fast run timer settings are correct. 25

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56

25
WARNING - DISCONNECT BATTERIES AND AC POWER BEFORE SERVICING ANY MECHANICAL OR MOVING COMPONENTS.
BATTERY CHECKOUT
When the batteries become weak the gate will begin to run noticeably slower.
NOTE:
Batteries should only be checked when you are sure they have had adequate time to fully charge.
1.
Turn off the AC power and run gate for 5 to 10 cycles while observing low battery indicator LED D12. If LED 12 comes ON, batteries are too weak
to function properly. If LED 12 does not light, then voltage should be checked as they still maybe near failure. Correct voltage is approximately 24.5
Vdc.
NOTE:
If LED D12 does light, gate will open to conserve batteries in this test
or in a real power loss, even if mode switch 8 on S2 is off.
Return of AC power will clear low battery indicator. Correct charge voltage is 27.5 Vdc with batteries not connected (set with R63, shown on the
Control Board Layout page).
GATE WILL NOT OPERATE.
Check the battery
connections.
Clear the active input to allow
the gate to open.
Clear the active
input to allow the
gate to close.
The max timer (MRT) has expired. Remove AC and battery power then
reapply to reset. Inspect the belt for slippage and verify the fast run
timer settings are correct.
Make sure the gate is not binding, then adjust the IRD.
Verify the gate reverses when obstructed.
Check fuse F4
Replace if blown.
Is the AC power
LED on now?
Check fuse F3,
Replace if
blown.
Allow operator to
charge before
operation.
Restore AC power
and/or turn AC power
switch ON.
Is the HBEAT
flashing now?
Is the AC PWR LED on?
Is the HBEAT flashing?
Yes
Yes
Yes
No
Is the “BAT LO” LED on?
Is S2-8 (open on AC fail) on?
Is the shadow input active?
Is the Safety, Back away, or
Open input active?
Does the IRD light while operating?
Is the IRD flashing?
No
No
Yes
No
Yes
No
No
No
No
Yes
Yes
Yes
No
Yes
TROUBLESHOOTING
GATE NOT OPERATING