HP R1.5 UPS R1500 XR Models User Guide - Page 30
Determining When to Replace Batteries, Obtaining New Batteries
View all HP R1.5 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 30 highlights
Battery Maintenance Determining When to Replace Batteries When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be replaced within 30 to 60 days. 1 100% 1 25% Figure 4-1. Bad Battery/Low Battery LED To check a battery alarm, initiate a UPS battery self-test to verify that battery replacement is required. If the Bad Battery/Low Battery LED (1) remains red, replace the batteries as soon as possible. NOTE: Depending on usage and environmental conditions, the batteries should last three to six years. For more information on initiating a self-test, refer to the section, "Initiating a Self-Test," in Chapter 2. Obtaining New Batteries New batteries may be required within 30 to 60 days when the Bad Battery/Low Battery LED illuminates red. Obtain spare batteries for the UPS when this occurs. HP supplies spare battery packs for this UPS. The UPS spare battery kit part number is 240789-001. CAUTION: Because of the short shelf life of the battery, avoid storing a battery spare as a backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep these batteries charged while in storage is implemented. 4-2 HP Uninterruptible Power System R1500 XR Models User Guide