Panasonic WU-144MF1U9E Service Manual - Page 69

CN001, E16 Alarm, Alarm code

Page 69 highlights

3. W-3WAY VRF Alarm Codes Trouble Diagnosis E16 Alarm Alarm code Alarm meaning Alarm conditions Probable cause Check Correction Example Notes E16 Automatic address setting alarm (too many units) • There were a number of indoor units was too many when Automatic address setting was performed. • After initial communications were completed, an unrecognized unit was detected. (1) The SW for setting the number of indoor units is incorrect. (2) The inter-unit control wiring is wired incorrectly. (1) Refer to the test run servicing materials and check the number of indoor units that is set. (2) Check the inter-unit control wiring at the indoor and outdoor units. After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic address setting again. - - E20 Alarm Alarm code E20 Alarm meaning No indoor units at automatic address setting. Alarm conditions When automatic address setting was performed, no indoor units were recognized. Probable cause (1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut. (2) Serial connector (OC: CN001) is disconnected at the outdoor unit. Check (3) The power is OFF at all indoor units in the system. (1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut. 1 (2) Check whether serial connector (OC: CN001) is disconnected at the outdoor unit. (3) Check the power at the indoor units. Correction (1) Reconnect the inter-unit control wire from the outdoor unit to the indoor unit. Example - Notes Position of serial connector (OC: CN001) on W-3WAY control PCB 2 CN001 3 4 E24 Alarm Alarm code E24 Alarm meaning Outdoor unit (main) failed to receive signal from other outdoor unit (sub). Alarm conditions After initial communications were completed, communications from an outdoor unit stopped. 5 Probable cause (1) After initial communications were completed, the outdoor unit main/sub control wiring was cut. (2) After initial communications were completed, the outdoor unit power was turned OFF. Check - Correction - Example - Notes - 6 7 3 - 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128

3
- 7
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
3
E16 Alarm
Alarm code
E16
Alarm meaning
Automatic address setting alarm (too many units)
Alarm conditions
• There were a number of indoor units was too many when Automatic address setting was performed.
• After initial communications were completed, an unrecognized unit was detected.
Probable cause
(1)
The SW for setting the number of indoor units is incorrect.
(2)
The inter-unit control wiring is wired incorrectly.
Check
(1)
Refer to the test run servicing materials and check the number of indoor units that is set.
(2)
Check the inter-unit control wiring at the indoor and outdoor units.
Correction
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
Example
Notes
E20 Alarm
Alarm code
E20
Alarm meaning
No indoor units at automatic address setting.
Alarm conditions
When automatic address setting was performed, no indoor units were recognized.
Probable cause
(1)
The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
(2)
Serial connector (OC: CN001) is disconnected at the outdoor unit.
(3)
The power is OFF at all indoor units in the system.
Check
(1)
Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
(2)
Check whether serial connector (OC: CN001) is disconnected at the outdoor unit.
(3)
Check the power at the indoor units.
Correction
(1)
Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.
Example
Notes
Position of serial connector (OC: CN001) on W-3WAY control PCB
E24 Alarm
Alarm code
E24
Alarm meaning
Outdoor unit (main) failed to receive signal from other outdoor unit (sub).
Alarm conditions
After initial communications were completed, communications from an outdoor unit stopped.
Probable cause
(1)
After initial communications were completed, the outdoor unit main/sub control wiring was cut.
(2)
After initial communications were completed, the outdoor unit power was turned OFF.
Check
Correction
Example
Notes
CN001