HP R1.5kVA HP UPS R3000 User Guide - Page 44
Utility power condition, Internal UPS fault condition, REPO condition, Site wiring condition,
View all HP R1.5kVA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 44 highlights
Utility power condition The utility input voltage is outside the operating range. Action: 1. Check the input voltage and reconfigure the UPS ("Configuring the UPS" on page 28). 2. Contact a qualified electrician to verify that the utility power is suitable for the UPS. Internal UPS fault condition Action: 1. Power down the UPS ("Powering down the UPS" on page 31). 2. If the condition persists, contact an HP authorized service representative. REPO condition Action: • If the remote switch is closed, then open the switch to enable power to the output receptacles. • If the condition occurred while reconnecting a disconnected REPO port, then verify the polarity of the REPO connector pins. For more information about REPO ports, see "Connecting the REPO port (on page 20)." Site wiring condition Action: Contact a qualified electrician to be sure that: • The utility power receptacle is grounded. • There is a ground wire in the UPS power cord. • The line and neutral wires are not reversed in the wall outlet. Overload condition All the load LEDs are illuminated. Action: 1. Power down the UPS ("Powering down the UPS" on page 31). 2. Remove one or more load devices to reduce the power requirements. 3. Wait at least 5 seconds and restart the UPS. 4. If the condition persists, verify that the load devices are not defective. UPS does not start Action: Troubleshooting 44