8. Specifications MODEL ENVIRONMENT Operation Temperature Operation Humidity Operation Altitude Acoustic Noise Level MANAGEMENT SNMP Multi-Functional LCD EPO (Emergency Power Off) Volt-Free Contacts Frequency Converter Mode STANDARDS Safety EMC Approvals SVT10KX Product specifications are subject to change without further notice. SVT20KX 0 ~ 40°C (For optimal battery life > 25°C)
31
8. Specifications
MODEL
SVT10KX
SVT20KX
SVT30KX
ENVIRONMENT
Operation Temperature
0 ~ 40°C (For optimal battery life > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude
<1000m
Acoustic Noise Level
Less than 65dB @ 1 Meter
MANAGEMENT
SNMP
Optional
Multi-Functional LCD
Standard
EPO (Emergency Power Off)
Standard
Volt-Free Contacts
Optional
Frequency Converter Mode
Programmable
STANDARDS
Safety
IEC/EN 62040-1
EMC
IEC/EN 62040-2 Category C3
Approvals
TUV
Product specifications are subject to change without further notice.
WIRING SPEC (AWG) [MM²]
MODEL
Input (Ph)
Output (Ph)
Neutral
Cable Length
Ground
SVT10KX
10 [5]
10 [5]
8 [8]
10M Max
8 [8]
SVT20KX
8 [8]
8 [8]
6 [13]
10M Max
6 [13]
SVT30KX
6 [10]
6 [10]
4 [21]
10M Max
4 [21]
UPS BLOCK DIAGRAM