Tripp Lite 9PX8KHW Eaton 9PX UPS 700-3000 VA 2U Owners Manual - Page 26
Connection with a HotSwap MBP module
View all Tripp Lite 9PX8KHW manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
3. Installation 3.9 Connection with a HotSwap MBP module (optional accessory) The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. 9PX 2000RT 1 238 4 5 6 9 11 10 7 28 MBP-120 29 33 34 35 36 LOAD 15 9PX 3000RT 1 238 4 5 6 1. Connect the input 36 on the HotSwap MBP module to the AC-power source. 2. C onnect the UPS input cable 1 to the "UPS Input socket" 35 on the HotSwap MBP module. 3. C onnect the UPS outlet 5 to the "UPS Output" 34 on the HotSwap MBP module (using the cable 28 supplied for G models). These cables and the connectors are marked in red. 4. C onnect the equipment to the outlets 29 on the HotSwap MBP module. These outlets differ, depending on the version of the HotSwap MBP module. Caution: when using HotSwap MBP, do not use UPS outlets to directly power equipment. As operating the bypass switch 33 will cut supply voltage to the equipment. * 9PX 700RT/ 9PX 1000RT / 9PX 1500RT: To connect to MBP-115, follow the same procedure as for the 9PX 2000RT / 9PX 3000RT. 9 11 10 7 28 MBP-130 29 LOAD 33 34 35 36 15 Page 26 9PX 1-3 KVA US_EN