Honeywell HM506DG115 Installation Guide - Page 35
See Manual Cleaning Cycle,
View all Honeywell HM506DG115 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 35 highlights
No. of Service LED Blinks 17 Fault Description Power to the wireless adapter overloaded. Auto-Recoverable? Yes, system will return to "Ready" if fault no longer exists in one hour. 18 Wireless Yes, system will communication return to "Ready" from wireless after one minute. adapter failed. Cleaning Tank was slow to N/A Required drain during last light automatic flush cycle is on. or 12-month cleaning interval time has expired. Steps to Fix (Performed Only By Professional HVAC Technician) 1. Verify wiring between TrueSTEAM and the wireless adapter. 2. Ensure DIP switches are set correctly. (DIP 3 up. Also DIP 4 up if TrueSTEAM R and C aren't wired.) 3. If the fault persists, replace the wireless adapter. 1. Verify wiring between TrueSTEAM and the wireless adapter. 2. Verify the Prestige control is operating correctly. 3. If the fault persists, replace wireless adapter and re-enroll connection to Prestige. Follow the tank cleaning steps. See "Manual Cleaning Cycle" on page 24. OPERATION AND SERVICE TrueSTEAM Humidification System 69-2285EF-01 33