HP R1.5 UPS R6000 Models User Guide - Page 39
Set Sync Range ± Hertz, Communications Setup, Table 3-6, Comm Setup Menu Options
View all HP R1.5 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 39 highlights
LCD Configuration and Status Set Sync Range ± Hertz Select Set Sync Range ± Hertz from the System Setup menu to set the sync range. • ±3.0 Hertz for normal mode • ±5.0 Hertz for extended mode Set Sync Range +/-3.0 Hz Communications Setup Select Comm Setup from the System Setup menu to configure a serial communication port. Comm Setup → Serial Port 1 Table 3-6 lists the options available under the Comm Setup menu for Port 1 and Port 2. Table 3-6: Comm Setup Menu Options LCD Display Serial Port x → Baud Rate Baud Rate * 1200 Serial Port x → Data Bits Data Bits x * 8 Serial Port x → Stop Bits Stop Bits x * 2 Serial Port x → Parity Parity x * odd Explanation Accesses the Baud Rate option. The current Baud Rate is displayed next to the asterisk (*). Select the desired rate from the list of 5 values: 1200, 2400, 4800, 9600, or 19200. Accesses the Data Bits option. The current Data Bits value is displayed next to the asterisk (*). Select the desired value for data bits: 7 or 8. Accesses the Stop Bits option. The current Stop Bits value is displayed next to the asterisk (*). Select the desired value for stop bits: 1 or 2. Accesses the Parity option. The current Parity value is displayed next to the asterisk (*). Select the desired value for parity: odd, even, none, mark, or space. 3-12 HP Uninterruptible Power System R6000 Models User Guide