Haier HPU-36CA03T3 Operation Manual - Page 27
valve,then
![]() |
View all Haier HPU-36CA03T3 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 27 highlights
■ Installation procedures 3. Piping connection of outdoor unit. Connect the connecting pipe and inlet and outlet liquid pipe according to the piping method. 4.Purging method Discharge the air out of the indoor unit and the refrigerant pipe by vacuumizing (1) Fasten all the nuts of the indoor and outdoor pipes to make these parts out of leakage. (2) Under the condition of the complete close of the indoor and outdoor valve center (both liquid and gas side),dismount the repair valve cap.Vacuumizing through the charge mouth of the repair valve. (3) After vacuumizing fasten the repair valve,and dismount the cap of the big and small stop valve,then loosen the stop valve center completely and fasten the big and small stop valve. 5.Extra charging amount of the refrigerant When piping is longer than 5 m, charge additional refrigerant specified in this list. Pipe length 5m 10m 15m Refrigerant charge (g) 325 650 20m 975 25m 1300 30m 1625 25