CyberPower RMCARD400 User Manual - Page 39

normal, eco10, eco15, generator, bypass

Page 39 highlights

Option rechargedelay rechargecap workmode returndelay Argument 0 | 60 | 120 | 180 | 300 | 600 | 1200 | 1800 | 3600 0 | 15 | 30 | 45 | 60 | 75 | 90 Description Set the recharge delay in seconds. When the utility power restores, the UPS will start to recharge until the specified delay is expired before restoring output power. Set the recharge capacity in percentage. When the utility power restores, the UPS will start to recharge until the specified battery capacity is met before restoring output power. normal-Normal working mode of the UPS. eco10%-On-line UPS enters Economy 10% mode. eco15%-On-line UPS enters Economy 15% mode. generator-If the UPS uses generator as its input power, this option should enable normal | eco10% | eco15% | the UPS to function normally. If this option generator | bypass is selected, the UPS will be forbidden to enter Bypass mode to protect the powered equipment. 0 ~ 600 bypass-Determines whether to allow the UPS to enter Manual Bypass mode. If this option is enabled, the UPS will be forced to enter Bypass mode. When the utility power restores, the UPS will start to recharge until the specified delay is expired before restoring output power. The numbers in the range 1 to 600 seconds are numbers divisible by 5. Example 1: To view the available value voltage this UPS output power can be set. CyberPower > upscfg supply? 100 110 115 Example 2: To define bypass condition as check utility voltage only CyberPower > upscfg bypasscond voltonly Example 3: To define UPS recharge delay as 2 minutes CyberPower > upscfg rechargedelay 120 Example 4: To set On-line UPS mode to generator mode CyberPower > upscfg mode generator 39

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72

39
Option
Argument
Description
rechargedelay
0 | 60 | 120 | 180 | 300 |
600 | 1200 | 1800 | 3600
Set the recharge delay in seconds. When
the utility power restores, the UPS will start
to recharge until the specified delay is
expired before restoring output power.
rechargecap
0 | 15 | 30 | 45 | 60 | 75 |
90
Set the recharge capacity in percentage.
When the utility power restores, the UPS
will start to recharge until the specified
battery capacity is met before restoring
output power.
workmode
normal | eco10% | eco15% |
generator | bypass
normal
-
Normal working mode of the UPS.
eco10%
-
On-line UPS enters Economy 10% mode.
eco15%
-
On-line UPS enters Economy 15% mode.
generator
-
If the UPS uses generator as
its input power, this option should enable
the UPS to function normally. If this option
is selected, the UPS will be forbidden to
enter Bypass mode to protect the powered
equipment.
bypass
-
Determines whether to allow the
UPS to enter Manual Bypass mode. If this
option is enabled, the UPS will be forced to
enter Bypass mode.
returndelay
0 ~ 600
When the utility power restores, the UPS will
start to recharge until the specified delay is
expired before restoring output power. The
numbers in the range 1 to 600 seconds are
numbers divisible by 5.
Example 1:
To view the available value voltage this UPS output power can be set.
CyberPower >
upscfg supply?
100
110
115
Example 2:
To define bypass condition as check utility voltage only
CyberPower >
upscfg bypasscond voltonly
Example 3:
To define UPS recharge delay as 2 minutes
CyberPower >
upscfg rechargedelay 120
Example 4:
To set On-line UPS mode to generator mode
CyberPower >
upscfg mode generator