Tripp Lite 5P850G Eaton 5P UPS Installation and User Manual - Page 13
English
View all Tripp Lite 5P850G manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
ENGLISH 2. Presentation In/Out settings ON/OFF settings Battery settings Description Load segments - Auto shutdown delay Overload prealarm Cold start Forced reboot Auto restart Energy saving Sleep mode Remote command RPO delay Automatic battery test Low battery warning Restart battery level Battery charge mode Deep discharge protection Available settings Default settings [Disable] [0s] [1 s] [2 s]...[65354 s] Group 1: Disable During a power outage, Group 2: Disable authorizes UPS to turn off power to equipment connected to Group 1 and/or Group 2 outlets. This feature allows the shedding of non-critical loads in order to conserve battery power for critical loads connected to the Primary group. [10 %] [15 %] [20 %] ... [100 %] [105 %] [105 %] Sets critical percentage of load where alarm overload alarm occurs. [Disable] [Enable] Enable Enables the product to be started on battery power. First cold start isw always disabled. [Disable] [Enable] Enable If mains recover during a shutdown sequence: - if enabled, shutdown sequence will complete and wait 10 seconds prior to restart - if disabled, shutdown sequence will not complete and restart will occur immediately. [Disable] [Enable] Enables the product to restart automatically when mains recovers after a complete battery discharge. Enable [Disable] [Enable] If enabled, UPS will shutdown after 5 min. of back-up time, if no load is detected on the output. Disable [Disable] [Enable] If disabled, LCD and communication will turn OFF immediately after UPS is OFF. If enabled, LCD and communication stays ON 1h30 min after UPS is OFF. Disable [Disable] [Enable] Enable If enabled, shutdown or restart commands from software are authorised. [0 s] [1s ] [2 s]...[180 s] [0 s] Delays remote power off command [No test] [Every day] [Every week] Every week [Every month] (in constant charge) Available only if battery charge mode otherwise following ABM is set to constant charge. [1 %] [2 %] ... [100 %] 20 % The alarm triggers when the set percentage of battery capacity is reached during a back-up time. [1 %] [2 %] ... [100 %] 0 % If set, automatic restart will occur only when percentage of battery charge is reached. [ABM cycling] [Constant charge] ABM cycling [Yes] [No] Yes If set to Yes, the UPS automatically prevents battery from deep discharge by adapting end of back-up time voltage threshold. 620-00082-01-us (en) Page 13