Panasonic WU-144MF1U9E CZ-256ESMC1U Intelligent Controller Installation Manual - Page 25

Setting central addresses, unit names and tenant numbers

Page 25 highlights

6 USING THE SYSTEM 5 2 Main Sub 6.3.3 Setting central addresses, unit names and tenant numbers Use this screen to set central addresses, names of units connected to the system and tenant numbers. Procedure Select 5.Initial settings in the main menu and 2.CNTR/Unit/Ten. No. in the sub menu, then proceed as follows. 1.Status/Control 2.Total data/Cut-off 3.Distrib. ratio/Usage 4.Maintenance/Test Run 5.Initial settings 6.Auxiliary settings 1.Date/Distrib. 2.CNTR/Unit/Ten. No. 3.Ten. name/Distrib. Gr. 4.Pulse meter setting 5.Clear accum. data A B C A When you touch a central address column, a screen will be displayed as shown on the right. Input a number 1 to 64 to set central address. When you touch [Auto], the central address will be automatically set. Two identical central address settings cannot be used within a link system. If you input an existing address, the input data is cancelled. It may take several minutes before the central address settings are reflected in the display. When other central controllers (system controller, etc.) are connected, it is recommended to set the central addresses on those units. 24 $;&4.$6@վJOEC

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101

24
6 USING THE SYSTEM
6.3.3 Setting central addresses, unit names and tenant numbers
Use this screen to set central addresses, names of units connected to the system and tenant
numbers.
Procedure
Select
5.Initial settings
in the main menu and
2.CNTR/Unit/Ten. No.
in the sub menu, then
proceed as follows.
A
When you touch a central address column, a screen will be displayed as shown on the right.
Input a number 1 to 64 to set central address.
When you touch [Auto], the central address will be automatically set.
Two identical central address settings cannot be used within a link system.
If you input an existing
address, the input data is cancelled.
It may take several minutes before the central address settings are re
ected in the display.
When other central controllers (system controller, etc.) are connected, it is recommended to set the
central addresses on those units.
Main
Sub
2
2
5
5
B
A
C
1.Status/Control
2.Total data/Cut-off
3.Distrib. ratio/Usage
4.Maintenance/Test Run
5.Initial settings
6.Auxiliary settings
1.Date/Distrib.
2.CNTR/Unit/Ten. No.
3.Ten. name/Distrib. Gr.
4.Pulse meter setting
5.Clear accum. data