Panasonic WU-144MF1U9E Solenoid Valve Kit Installation - Page 4
Wring, indoor, connect, supplied, wires, supplied, Class, WARNING
![]() |
View all Panasonic WU-144MF1U9E manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 4 highlights
3. Wiring Indoor Unit Solenoid valve relay kit 5P connector ELECTRICAL BOX Indoor PCB Class I field supplied Power Wring from indoor unit PCB 3-Way connect wire (6.5ft ) / supplied G 1 2 3 4 5 Terminal base 5 wires / field supplied (Class II , 98ft Max.) It requires that the Class I wire and Class II wire should be separated. Solenoid valve kit 1 2 G 1 2 3 4 5 Terminal base 4. Procedure : 1. Connect the power supply wire to the solenoid valve kit, 0 using the Class I wire. 2. Connect the solenoid valve kit to the solenoid valve relay kit, using the Class II wire. 3. Connect the solenoid valve relay kit to the indoor unit, using the supplied connect wire. E 4. The left-over wires connected to the solenoid valve relay kit should be tied up in a bundle of wires by the supplied wire holder not to leave the wires loose as shown in the diagram at right. 3-Way connect wire (supplied) 5 wires / field supplied (Class II, 98ft Max.) • I 5. Installation to the Solenoid Valve Relay Kit Install the solenoid valve relay kit into the indoor unit and fix it using a Philips-head screwdriver. See the diagram in the section of "6. Electrical Wiring Diagrams". WARNING • Do not install outside the building and the area where the water is splashed. Failure to do so could result in product or property damage. • Do not handle or touch the unit with wet hands. Failure to do so could result in electric shock. 4