Panamax BATT1500-EXT Manual - Page 12

Set Meter Brightness, Set Display Scroll Mode, Set Display Sleep Mode, Reset Factory Settings, Send

Page 12 highlights

SET METER BRIGHTNESS Sets the LCD display and outlet bank indicator brightness. Send to UPS: !SET_BRIGHT xxx xxx = {100, 075, 050, 025} If specified brightness setting is invalid Action: No action will be taken, UPS will request a valid brightness setting Response from UPS: $INVALID_PARAMETER $BRIGHTNESS = xxx SET DISPLAY SCROLL MODE Sets the LCD display SCROLL mode Send to UPS: !SET_SCROLLMODE xxx xxx = {5SEC, 10SEC, OFF} If specified display scroll mode is invalid Action: No action will be taken, UPS will request a valid mode setting Response from UPS: $INVALID_PARAMETER $SCROLL_MODE = xxx SET DISPLAY SLEEP MODE Set the LCD display SLEEP mode Send to UPS: !SET_SLEEPMODE xxx xxx = {30SEC, 60SEC, OFF} If specified display sleep mode is invalid Action: No action will be taken, UPS will request a valid mode setting Response from UPS: $INVALID_PARAMETER $SLEEP_MODE = xxx RESET FACTORY SETTINGS Resets all of the custom configuration settings Send to UPS: !RESET_ALL Action: Sets all state variables to the default values Response from UPS: $FACTORY SETTINGS RESTORED SEND QUERIES IDENTIFY Request that the unit identify itself. Send Query to UPS: ?ID Action: Model number and firmware revision will be provided. Response: $PANAMAX $MB1500 $FIRMWARE revision OUTLET STATUS Requests the on/off status of the outlet banks Send Query to UPS: ?OUTLETSTAT status = {ON, OFF} Action: On/off status for outlets will be provided. Response: $BANK1 = status $BANK2 = status $BANK3 = status $BANK4 = status POWER STATUS Requests the status of the input voltage. The responses are the same as Power Fault Status Change. Send Query to UPS: ?POWERSTAT Action: Power status messages will be returned Response: Normal operation = $PWR = NORMAL Overvoltage $PWR = OVERVOLTAGE Undervoltage $PWR = UNDERVOLTAGE Lost Power $PWR = LOST POWER Test Mode $PWR = TEST POWER Requests the input and output voltages Send Query to UPS: ?POWER Action: Voltage status messages will be displayed Response: $VOLTS_IN = vvv $VOLTS_OUT = vvv $WATTS = xxxx $VA = xxxx xxx is expressed in decimal format. If the value is less than 100, the hundreds digit is represented with a 0. For example a line voltage of 92VAC would be expressed as: $VOLTAGE = 092 10

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45

10
SET METER BRIGHTNESS
Sets the LCD display and outlet bank indicator brightness.
Send to UPS: !SET_BRIGHT xxx<CR>
xxx = {100, 075, 050, 025}
If specified brightness setting is invalid
Action: No action will be taken, UPS will request a valid brightness setting
Response from UPS: $INVALID_PARAMETER<CR>
$BRIGHTNESS = xxx<CR>
SET DISPLAY SCROLL MODE
Sets the LCD display SCROLL mode
Send to UPS: !SET_SCROLLMODE xxx<CR>
xxx = {5SEC, 10SEC, OFF}
If specified display scroll mode is invalid
Action: No action will be taken, UPS will request a valid mode setting
Response from UPS: $INVALID_PARAMETER<CR>
$SCROLL_MODE = xxx<CR>
SET DISPLAY SLEEP MODE
Set the LCD display SLEEP mode
Send to UPS: !SET_SLEEPMODE xxx<CR>
xxx = {30SEC, 60SEC, OFF}
If specified display sleep mode is invalid
Action: No action will be taken, UPS will request a valid mode setting
Response from UPS: $INVALID_PARAMETER<CR>
$SLEEP_MODE = xxx<CR>
RESET FACTORY SETTINGS
Resets all of the custom configuration settings
Send to UPS: !RESET_ALL<CR>
Action: Sets all state variables to the default values
Response from UPS: $FACTORY SETTINGS RESTORED<CR>
SEND QUERIES IDENTIFY
Request that the unit identify itself.
Send Query to UPS: ?ID<CR>
Action: Model number and firmware revision will be provided.
Response: $PANAMAX<CR>
$MB1500<CR>
$FIRMWARE revision<CR>
OUTLET STATUS
Requests the on/off status of the outlet banks
Send Query to UPS: ?OUTLETSTAT<CR>
status = {ON, OFF}
Action: On/off status for outlets will be provided.
Response: $BANK1 = status<CR>
$BANK2 = status<CR>
$BANK3 = status<CR>
$BANK4 = status<CR>
POWER STATUS
Requests the status of the input voltage. The responses are the same as
Power Fault Status Change.
Send Query to UPS: ?POWERSTAT<CR>
Action:
Power status messages will be returned
Response:
Normal operation = $PWR = NORMAL<CR>
Overvoltage $PWR = OVERVOLTAGE<CR>
Undervoltage $PWR = UNDERVOLTAGE<CR>
Lost Power $PWR = LOST POWER<CR>
Test Mode $PWR = TEST<CR>
POWER
Requests the input and output voltages
Send Query to UPS: ?POWER<CR>
Action: Voltage status messages will be displayed
Response: $VOLTS_IN = vvv<CR>
$VOLTS_OUT = vvv<CR>
$WATTS = xxxx<CR>
$VA = xxxx<CR>
xxx is expressed in decimal format. If the value is less than 100, the hundreds
digit is represented with a 0. For example a line voltage of 92VAC would be
expressed as: $VOLTAGE = 092<CR>