5. PHYSICAL CABLING SPECIFICATIONS Component: Existing cabling is CAT 6 or greater for new installations. (CAT 5e is adequate for existing installations.) The cabling from router to connected access installation point is less than 300' cabling length. Patch Cable follows configuration (for router or switch) in Fig. 1 on the next page. Result (Circle) Yes / No Yes / No Yes / No Verified √: ❏ ❏ ❏ Action Needed If No, recabling using CAT 6 or greater is required. Consult with your service provider to replace the cable. If No, you need to adjust and shorten the distance between the internet router and the unit. Date Completed The outlet for the CAPX-system MUST be an external dedicated 120 Vac outlet. Refer to the table below for maximum wire run distances. This outlet should be wired back to its own 10 Amp minimum circuit breaker. WIRE SPECIFICATION 14 AWG MAXIMUM RUN DISTANCE Up to 300 feet (91.4 m) NOTE: Main power supply and control wiring MUST be run in separate conduits. Conduits must be UL approved for low and high voltage. Refer to the NEC for additional wiring requirements. 16 AWG 18 AWG Up to 200 feet (60.9 m) Up to 100 feet (30.4 m) IMPORTANT: An earth ground rod is strongly recommended and should be no further than 12 feet (3.7 m) from the CAPX-system and use a minimum of 12 gauge wire in most cases. The type and length of earth ground rods vary by region. Contact the AHJ (Authority Having Jurisdiction) in the municipality where you plan to install the CAPX-system for correct grounding materials and installation procedures. A proper ground is critical to minimizing risk for the CAPX-system from damaging electrical transients. 6. ACCOUNT SETUP myQ COMMUNITY Action: 1a. For existing accounts, create a myQ Community. 1b. Call LiftMaster Tech Support - Access Control at 877-247-6764 to set up a myQ Community account. 2. Respond within 24 hours to the email invitation to register. 3. Proceed within your account to complete: FACILITY (your site profile - ALL REQUIRED FIELDS) PEOPLE (including residents and credentials) Verified √: ❏ ❏ ❏ Action Needed Date Completed 3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

3
6. ACCOUNT SETUP myQ COMMUNITY
Action:
Verified √:
Action Needed
Date
Completed
1a.
For existing accounts, create a myQ Community.
1b. Call LiftMaster Tech Support - Access Control at 877-247-6764 to
set up a myQ Community account.
2.
Respond within 24 hours to the email invitation to register.
3.
Proceed within your account to complete:
FACILITY
(your site profile - ALL REQUIRED FIELDS)
PEOPLE
(including residents and credentials)
5. PHYSICAL CABLING SPECIFICATIONS
Component:
Result
(Circle)
Verified √:
Action Needed
Date
Completed
Existing cabling is CAT 6 or greater for new
installations. (CAT 5e is adequate for existing
installations.)
Yes
/
No
If
No
, recabling using CAT 6 or
greater is required. Consult with your
service provider to replace the cable.
The cabling from router to connected access
installation point is less than 300' cabling
length.
Yes
/
No
If
No
, you need to adjust and shorten
the distance between the internet
router and the unit.
Patch Cable follows configuration (for router
or switch) in Fig. 1 on the next page.
Yes
/
No
The outlet for the CAPX-system MUST be an external dedicated 120 Vac outlet. Refer
to the table below for maximum wire run distances. This outlet should be wired back to
its own 10 Amp minimum circuit breaker.
NOTE
: Main power supply and control wiring MUST be run in separate
conduits. Conduits must be UL approved for low and high voltage. Refer to the
NEC for additional wiring requirements.
IMPORTANT
: An earth ground rod is strongly recommended and should be no further than 12 feet (3.7 m) from the CAPX-system and use a
minimum of 12 gauge wire in most cases. The type and length of earth ground rods vary by region. Contact the AHJ (Authority Having Jurisdiction) in
the municipality where you plan to install the CAPX-system for correct grounding materials and installation procedures. A proper ground is critical to
minimizing risk for the CAPX-system from damaging electrical transients.
WIRE SPECIFICATION
MAXIMUM RUN DISTANCE
14 AWG
Up to 300 feet (91.4 m)
16 AWG
Up to 200 feet (60.9 m)
18 AWG
Up to 100 feet (30.4 m)