HP R7000 HP UPS R5000 User Guide - Page 52

Battery specifications, Average battery runtime, Minimum battery runtime

Page 52 highlights

Feature Surge suppression Noise filtering Specification High-energy 6500 A peak MOVs and line filter for normal and common mode use Battery specifications Feature Type Voltage Charging Specification Each model contains maintenance-free, sealed, valve regulated lead-acid batteries with an 8-year minimum float service life at 25°C (77°F). The battery modules have a battery string voltage of 216 V. Complete charge takes no more than 48 hours. Approximately 3 hours to 80 percent capacity at default nominal utility voltage and no load. Average battery runtime Average battery runtimes are approximate and vary depending on connected equipment, configuration, battery age, temperature, and so on. These estimates are based on the batteries at beginning of life. Load % Estimated Runtime with battery runtime one ERM (minutes) (minutes) 20 44 123 50 16 44 80 7 25 100 5.7 20 * NA/JPN model only Runtime with four ERMs (minutes)* 436 145 83 64 Minimum battery runtime Minimum battery runtimes are at beginning of life. Load % Internal battery Runtime with runtime one ERM (minutes) (minutes) 20 36 100 50 12 36 80 6 23 100 5 18 * NA/JPN model only Runtime with four ERMs (minutes)* 360 115 80 58 Specifications 52

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62

Specifications 52
Feature
Specification
Surge suppression
High-energy 6500 A peak
Noise filtering
MOVs and line filter for normal and common mode
use
Battery specifications
Feature
Specification
Type
Each model contains maintenance-free, sealed, valve
regulated lead-acid batteries with an 8-year minimum float
service life at 25°C (77°F).
Voltage
The battery modules have a battery string voltage of 216 V.
Charging
Complete charge takes no more than 48 hours.
Approximately 3 hours to 80 percent capacity at default
nominal utility voltage and no load.
Average battery runtime
Average battery runtimes are approximate and vary depending on connected equipment, configuration,
battery age, temperature, and so on. These estimates are based on the batteries at beginning of life.
Load %
Estimated
battery runtime
(minutes)
Runtime with
one ERM
(minutes)
Runtime with
four ERMs
(minutes)*
20
44
123
436
50
16
44
145
80
7
25
83
100
5.7
20
64
* NA/JPN model only
Minimum battery runtime
Minimum battery runtimes are at beginning of life.
Load %
Internal battery
runtime
(minutes)
Runtime with
one ERM
(minutes)
Runtime with
four ERMs
(minutes)*
20
36
100
360
50
12
36
115
80
6
23
80
100
5
18
58
* NA/JPN model only