HP R/T2200 IEC-320-C14 HP Uninterruptible Power System T700 Models User Guide - Page 44

Overcurrent Protection, Battery Specifications, Battery Runtime, Table C-5, Estimated Battery Runtime

Page 44 highlights

Specifications Overcurrent Protection Table C-5: Overcurrent Protection UPS Model T700 NA T700 JPN T700 H INT'L Input Protection Input Overload Protector Input Overload Protector Input Overload Protector Battery Specifications Table C-6: Battery Specifications Feature Type Voltage Charging Specification Sealed lead-acid; maintenance-free 24-V Battery String HP recommends 24 hours to allow full charge Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load Battery Runtime Table C-7: Estimated Battery Runtime Load (VA) Load (Watts) Estimated Battery Runtime (Minutes) 200 128 38 300 192 27 500 320 14 600 402 9 700 500 6 Note: Battery times are approximate and may vary depending on the load configuration and battery charge. Before connecting devices, verify that the UPS will not overload by checking that the rating of the devices does not exceed the capacity of the UPS. After verifying that the UPS will not overload, connect the power cords from the devices to the appropriate output receptacles of the UPS. HP Uninterruptible Power System T700 Models User Guide C-3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

Specifications
HP Uninterruptible Power System T700 Models User Guide
C-3
Overcurrent Protection
Table C-5:
Overcurrent Protection
UPS Model
Input Protection
T700 NA
Input Overload Protector
T700 JPN
Input Overload Protector
T700 H INT’L
Input Overload Protector
Battery Specifications
Table C-6:
Battery Specifications
Feature
Specification
Type
Sealed lead-acid; maintenance-free
Voltage
24-V Battery String
Charging
HP recommends 24 hours to allow full charge
Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load
Battery Runtime
Table C-7:
Estimated Battery Runtime
Load (VA)
Load (Watts)
Estimated Battery Runtime (Minutes)
200
128
38
300
192
27
500
320
14
600
402
9
700
500
6
Note:
Battery times are approximate and may vary depending on the load configuration and battery
charge.
Before connecting devices, verify that the UPS will not overload by checking that the rating
of the devices does not exceed the capacity of the UPS.
After verifying that the UPS will not overload, connect the power cords from the devices to
the appropriate output receptacles of the UPS.