HP R/T2200 IEC-320-C14 HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 - Page 33
Battery, Battery Runtimes in Minutes
![]() |
View all HP R/T2200 IEC-320-C14 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 33 highlights
SPECIFICATIONS Table 8 Battery UPS Configuration Voltage Type Charging Monitoring HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc Sealed, maintenance‐free, valve‐regulated, lead‐acid Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line and no supplementary power supply load Advanced monitoring for earlier failure detection and warning Table 9 Battery Runtimes (in Minutes) UPS Models by VA Ratings Load (VA) Watts 750 1000 200 128 38 41 300 192 27 28 500 320 14 15 600 402 9 10 750 503 6 8 900 603 6 1000 670 5 1200 804 1400 938 NOTE Battery times are approximate and may vary depending on the load configuration and battery charge. 1400 58 41 28 19 14 10 8 6 5 26 HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002