HP R/T2200 IEC-320-C14 HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 - Page 33

Battery, Battery Runtimes in Minutes

Page 33 highlights

SPECIFICATIONS Table 8 Battery UPS Configuration Voltage Type Charging Monitoring HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc Sealed, maintenance‐free, valve‐regulated, lead‐acid Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line and no supplementary power supply load Advanced monitoring for earlier failure detection and warning Table 9 Battery Runtimes (in Minutes) UPS Models by VA Ratings Load (VA) Watts 750 1000 200 128 38 41 300 192 27 28 500 320 14 15 600 402 9 10 750 503 6 8 900 603 6 1000 670 5 1200 804 1400 938 NOTE Battery times are approximate and may vary depending on the load configuration and battery charge. 1400 58 41 28 19 14 10 8 6 5 26 HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38

SPECIFICATIONS
HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide
S
505922-002
26
Table 8
Battery
UPS Configuration
HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries
HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries
HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries
Voltage
HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc
HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc
Type
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging
Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line
and no supplementary power supply load
Monitoring
Advanced monitoring for earlier failure detection and warning
Table 9
Battery Runtimes (in Minutes)
UPS Models by VA Ratings
Load (VA)
Watts
750
1000
1400
200
128
38
41
58
300
192
27
28
41
500
320
14
15
28
600
402
9
10
19
750
503
6
8
14
900
603
6
10
1000
670
5
8
1200
804
6
1400
938
5
NOTE
Battery times are approximate and may vary depending on the load configuration and battery charge.