BLOWER PERFORMANCE CFM versus Static Pressure (inches of water column dry coil w/ filter) 4% reduction for wet coil. Model Static Pressure 0.1 CFM 0.15 0.2 2 Ton High 900 877 856 Middle 630 614 599 0.25 0.3 0.35 0.4 0.5 835 816 795 766 737 585 571 556 536 515 3 Ton High ------ 1240 1208 1177 1148 1121 1091 1061 Low ------ 1125 1093 1062 1033 1006 976 946 4 Ton 5 Ton 5 Ton-E High Low -----1480 High Low High Low 1650 1605 1560 1515 1470 1425 1442 1404 1366 1328 1290 1252 1800 1745 1690 1635 1580 1525 1850 1795 1740 1685 1630 1575 The air delivery can be varied by changing the blower speeds. This can allow for differences encountered in installations. The CFM can be checked by the following method; (The optional Heat Kit must be installed to continue with this procedure.) 1) All access panels must be in place. 2) Start the unit in the heat mode. 3) Measure the return air temperature. 4) Measure the supply temperature. This measurement should be done in various locations to obtain an average. 5) Subtract the return temperature from the supply temperature. This is referred to as the temperature rise. 6) Measure the actual supply voltage and actual amperage at the terminal block/circuit breaker. 7) The BTUH output = (Voltage x Amps x 3.41) output (BTUH) CFM = 1.08 X temperature rise Should the CFM need to be increased or decreased it may be done by adjusting the blower speed tap as shown on the wiring diagram. 14