GE AJCH12DC Owners Manual - Page 12

If Something Goes Wrong, Before You Call for Service

Page 12 highlights

If Something Goes Wrong Before You Call for Service Problem Air Conditioner Doesn't Start Possible Causes The air conditioner is unplugged The fuse is blown/circuit breaker is tripped Power failure What to Do • Make sure the air conditioner plug is pushed completely into the outlet. • Check the house fuse/circuit breaker box and replace fuse or reset the breaker. • If power failure occurs, turn the mode control to OFF. When power is restored, wait 3 minutes to restart the air conditioner to prevent tripping of the compressor overload. • There is a protective time delay (up to 3 minutes) in the heat/cool and heat pump models. Wait 3 minutes for the air conditioner to resume heating or cooling. Air Conditioner Does Not Cool or Heat as it Should Airflow is restricted The thermostat control may not be set high or low enough The air filter is dirty The room may have been hot or cold Cold air is escaping Cooling coils have iced up • Make sure there are no curtains, blinds or furniture blocking the front of the air conditioner. • Turn the knob to a warmer or cooler setting. The coolest setting provides maximum cooling. The warmest setting provides maximum heating on models with heat. • Clean the filter at least every 30 days. See the Care and Cleaning section. • When the air conditioner is first turned on you need to allow time for the room to cool down or warm up. • Check for open furnace floor registers and cold air returns. • Set the exhaust vent in the closed position. • See freezing up below. Air Conditioner Freezing Up 12 Ice blocks the airflow and stops the air conditioner from cooling the room • Set the mode control at HIGH FAN or HIGH COOL with the thermostat at a warmer setting.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

12
Air Conditioner
Doesn’t Start
Air Conditioner Does
Not Cool or Heat as
it Should
The air conditioner
Make sure the air conditioner plug is
is unplugged
pushed completely into the outlet.
The fuse is blown/circuit
Check the house fuse/circuit breaker
breaker is tripped
box and replace fuse or reset the
breaker.
Power failure
If power failure occurs, turn the mode
control to
OFF
. When power is restored,
wait 3 minutes to restart the air conditioner
to prevent tripping of the compressor
overload.
There is a protective time delay (up to 3
minutes) in the heat/cool and heat pump
models. Wait 3 minutes for the air
conditioner to resume heating or cooling.
Problem
Possible Causes
What to Do
Air Conditioner
Freezing Up
Ice blocks the airflow
Set the mode control at
HIGH FAN
or
and stops the air conditioner
HIGH COOL
with the thermostat
from cooling the room
at a warmer setting.
Airflow is restricted
Make sure there are no curtains, blinds
or furniture blocking the front of the
air conditioner.
The thermostat control
Turn the knob to a warmer or cooler setting.
may not be set high
The coolest setting provides maximum
or low enough
cooling. The warmest setting provides
maximum heating on models with heat.
The air filter is dirty
Clean the filter at least every 30 days.
See the Care and Cleaning section.
The room may have been hot
When the air conditioner is first turned on
or cold
you need to allow time for the room to
cool down or warm up.
Cold air is escaping
Check for open furnace floor registers and
cold air returns.
Set the exhaust vent in the closed position.
Cooling coils have iced up
See freezing up below.
If Something Goes Wrong
Before You Call for Service