Electrical work

Page 13 highlights

Electrical work Electric safety regulations for the initial Installation 1. If there is serious safety problem about the power supply, the technicians should refuse to install the air conditioner and explain to the client until the problem is solved. 2. Power voltage should be in the range of 90%~110%of rated voltage. 5. According to the attached Electrical Connection Diagram located on the panel of the outdoor unit to connect the wire. 6. All wiring must comply with local and national electrical codes and be installed by qualified and skilled electricians. 3. The circuit protector and main power switch with a 1.5 times capacity of Max. Current of the unit should be installed in power circuit. 4. Ensure the air conditioner is grounded well. 7. An individual branch circuit used only for this air conditioner must be available. See the following table for suggested wire sizes and fuse specifications: CAPACITY POWER SUPPLY INPUT RATED AMP AWG WIRE Switch / Fuse SIZE < 9000 Btu's 115V~/ 60Hz 25A/25A 12 9000 Btu's < capacity < 12000 Btu's 115V~/ 60Hz 25A/25A 12 > 12000 Btu's 208/230V~/ 60Hz 25A/25A 12 Note: The supply voltage must be consistent with the rate voltage of the air conditioner. Electrical work 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21

Note: The supply voltage must be consistent with the rate voltage of the air conditioner.
Electrical work
1. If there is serious safety problem
about the power supply, the
technicians should refuse to install
the air conditioner and explain to the
client until the problem is solved.
2. Power voltage should be in the
range of 90%~110%of rated
voltage.
3. The
circuit
protector and main
power switch with a 1.5 times
capacity of Max. Current of the unit
should be installed in power circuit.
4. Ensure the air conditioner is
grounded well.
5. According to the attached
Electrical Connection Diagram
located on the panel of the
outdoor unit to connect the wire.
6. All wiring must comply with local
and national electrical codes and
be installed by qualified and
skilled electricians.
7. An individual branch circuit
used only for
this air conditioner
must be
available. See the
following table
for suggested wire
sizes and fuse
specifications:
Electric safety regulations for the initial Installation
Electrical work
INPUT RATED AMP
Switch / Fuse
POWER SUPPLY
SIZE
CAPACITY
<
9000
Btu's
9
000
Btu's
<
capacity
<
12000 Btu’s
> 12000 Btu's
115V~/ 60Hz
115V~/ 60Hz
208/230V~/ 60Hz
25
A
/25
A
25
A
/25
A
25
A
/25
A
AWG WIRE
1
12
18
2
12