    Order No: PAPAMY1604052CE Installation Manual Indoor Unit CS-E9SD3UAW CS-E12SD3UAW CS-E18SD3UAW Outdoor Unit CU-E9SD3UA CU-E12SD3UA CU-E18SD3UA Destination USA WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public.
  • Panasonic CS-E9SD3UAW | install manual - Page 2
    11. Installation Instruction x IMPORTANT (ONLY FOR E9SD3UAW AND E12SD3UAW) This product has been designed and manufactured to meet ENERGY STAR® criteria (12.7 mm) 1/4" (6.35 mm) 5/8" (15.88 mm) 1/4" (6.35 mm) x Pipe size reducer (CZ-MA1P) for outdoor Multi connection CS-E12SD3UAW, CS-E18SD3UAW 33
  • Panasonic CS-E9SD3UAW | install manual - Page 3
    17200 (12.7 mm) 9.8 ft (3 m) 65.6 ft (20 m) 0.2 oz/ft (20 g/m) 24.6 ft (7.5 m) 0.3 100.0 ft oz/ft (30.5 m) (25 g/m) 32.8 ft (10 m) Example: For E9SD3UAW If the unit is installed at 32.8 ft (10 m) distance, the quantity of additional refrigerant should be 1.64 oz (50 g) .... (32.8 - 24.6) ft
  • Panasonic CS-E9SD3UAW | install manual - Page 4
    location x Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. x The location should be strong enough to support the main unit without vibration. x There should not be any heat or steam source nearby. x Drainage should be easy. Avoid locating the drain port
  • Panasonic CS-E9SD3UAW | install manual - Page 5
    Required Minimum Space for Installation and Service 22 7/32" (564) Min. 7 7/8" (200) o r more 32 7/16" (824) (Suspension bolt pitch) Min. 7 7/8" (200) or more Electrical component box Inspection access 17 23/32" x 17
  • Panasonic CS-E9SD3UAW | install manual - Page 6
    ") (60 to 90 mm) Approx. 4 1/2" (144) Hanging bolt M10 Roof beam Ceiling surface x Secure the hanging bolts (M10, locally purchased) firmly in a manner capable of supporting the unit weight. x Consult your construction or interior contractor for details on finishing the ceiling opening. 37
  • Panasonic CS-E9SD3UAW | install manual - Page 7
    Installing an Intake and Discharge Duct Type x Ensure the range of unit external static pressure is not exceeded. Refer technical manual for the range of external static pressure setting. x Connect the duct as shown. x When attaching duct to the intake side, remove the product filter frame
  • Panasonic CS-E9SD3UAW | install manual - Page 8
    Mounting Remote Controller Receiver Install the remote controller receiver cable at least 1 31/32" (50 mm) away from electric wires of other appliances to avoid miss-operation (electromagnetic noise). 1 Remove the bottom case. Attention Mounting the bottom case x Tighten the screws securely until
  • Panasonic CS-E9SD3UAW | install manual - Page 9
    x Connect the indoor unit and the remote control receiver 5. (Refer to the illustration.) x Fix the green wire from receiver cable 8 to the grounding location provided inside control board. Receiver cable 8 Control box Remote control receiver 5 11.1.4 Connecting the Drain Piping x Lay the drain
  • Panasonic CS-E9SD3UAW | install manual - Page 10
    11.1.6 Connect the Cable to the Indoor Unit x Remove control box cover. x Remove the plugs. x Fix the conduit connections to the knockout holes together with lock nuts, then secure them against the control box side panel. x Receiver cable wires 8 must pass through the upper conduit hole. Make sure
  • Panasonic CS-E9SD3UAW | install manual - Page 11
    11.1.6.1 Wire Stripping and Connecting Requirement Wire stripping No loose strand when inserted 13/32" ± 1/32" 10 ± 1 mm Indoor/outdoor connection terminal board 7/32" (5 mm) or more (gap between wires) Conductor Conductor Conductor not fully inserted over inserted fully inserted ACCEPT
  • Panasonic CS-E9SD3UAW | install manual - Page 12
    ) Wrench (Adjustable Wrench) Flare Nut (Connection pipe) Female side Applicable to Liquid and Gas side of CS-E9SD3UAW Torque Wrench for Flare Nut Liquid side of CS-E12SD3UAW CS-E18SD3UAW Male side Pipe Size Hall Union Packing Reducer Flare Nut Female side (Auxiliary pipe) (Connection pipe
  • Panasonic CS-E9SD3UAW | install manual - Page 13
    close the low side valve of the charging set and turn off the vacuum pump. 5 Disconnect the vacuum pump house from the service port of the 3-way valve. 6 Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf•ft (18 N•m) with a torque wrench. 7 Remove the valve caps of
  • Panasonic CS-E9SD3UAW | install manual - Page 14
    Connect the cable to the Outdoor Unit x For model E9SD3UAW, E12SD3UAW Top Panel 1 Remove Top panel. 2 Remove original position with the screws. 11 For wire stripping and connection requirement, refer to instruction 11.1.6 of indoor unit. Earth wire longer than other AC wires for safety reasons
  • Panasonic CS-E9SD3UAW | install manual - Page 15
    and control board cover (metal and resin) to the original position with the screws. 11 For wire stripping and connection requirement, refer to instruction 11.1.6 of indoor unit. Terminal Board Earth wire longer than others AC wires for safety reasons Holder Terminal Board Earth wire longer than
  • Panasonic CS-E9SD3UAW | install manual - Page 16
    11.2.6 Piping Insulation 1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2 If drain hose or connecting piping is in the room (where dew may form),
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

© Panasonic Corporation 2016
Order No: PAPAMY1604052CE
Indoor Unit
Outdoor Unit
CS-E9SD3UAW
CS-E12SD3UAW
CS-E18SD3UAW
CU-E9SD3UA
CU-E12SD3UA
CU-E18SD3UA
Destination
USA
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the product or products dealt with in this service information by anyone else could result in serious injury or death.
WARNING
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.