Dell DS-32M2 Installation Guide

Dell DS-32M2 Manual

Dell DS-32M2 manual content summary:

  • Dell DS-32M2 | Installation Guide - Page 1
    It also describes the kits available for mounting them in EMC and non-EMC racks and includes installation instructions as well. Device Device Model 16-Port Departmental Switch (2Gb) DS-16M2-0D 32-Port Departmental Switch (2Gb) DS-32M2-0D Mounting Kit Model DS16M-CRKH/CRKL DS32M-CRKH/CRKL Major
  • Dell DS-32M2 | Installation Guide - Page 2
    switch. There are no restrictions on the location of the DS-32M2 switches in the rack/cabinet. Power distribution must support the number of outlets required for the switch and the switch power rating listed in the table on page 2. 2 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 3
    in round-hole channels (8) 3 per rail for DS-32M in round-hole channels (6) 4 per rail for DS-16M in square-hole channels (8) 3 per rail for DS-32M in square-hole channels (6) 1 per bracket, used to secure brackets to the rails (2) EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 3
  • Dell DS-32M2 | Installation Guide - Page 4
    Switch Mounting Kit (DS-16M or DS-32M) Component #10 washers ball studs Latch brackets and keyplate spacers Use 1 washer and 1 ball rails and switch(es). ◆ # 1 Phillips head screwdriver ◆ 1/4-in. nut driver ◆ 5/16-in. nut driver 4 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 5
    the installation procedures for the DS-16M and DS-32M rails. The figures below show a front and rear view of four sets of rails installed in a 39U rack. Note that the rack is shown without the side skins. Front View Rear View EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 5
  • Dell DS-32M2 | Installation Guide - Page 6
    are installing both a DS-16M2 and DS-32M2 switch, the DS-16M2 should be positioned at the top of the rack/cabinet, located above the DS-32M2 switch. Select the appropriate length rails, and follow the steps below to install them. 6 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 7
    Installing the DS-16M and DS-32M Rails 1. Assemble the rails. The rails assembly consists of an adjustable rail, a C channel, and two correctly when this word "top" is up and toward the rack/cabinet front. See the next figure. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 7
  • Dell DS-32M2 | Installation Guide - Page 8
    Installing the DS-16M and DS-32M Rails "Top" up and to the rack front 3. Adjust the length of the rail to fit between screws (see the table on page 3), or secure the rail to a square-hole channel with 2 square-hole washers and 8 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 9
    an L or an R will be upright when correctly installed on the left or right channel. See the figure below. Switch Mounting Rails Spacer Screw (2) EMC2424 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 9
  • Dell DS-32M2 | Installation Guide - Page 10
    DS-16M and DS-32M Rails 7. If you are installing the switch in a 39U cabinet, position the #10 washer and ball stud in the center hole, between the two M5 x 12 mm screws. Hand-tighten the ball stud. NOTE: The ball studs support 10 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 11
    . See the figures below. DS-16M Round-Hole Channel, Rack Rear (for example, CLARiiON Rack/Cabinet) DS-16M Square-Hole Channel, Rack Rear (for example, Third Party Rack/Cabinet) 10. Repeat steps 1 through 9 for the other rail. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 11
  • Dell DS-32M2 | Installation Guide - Page 12
    four screw holes. See the figure below. Front Flange Rear Flange NOTE: If you are installing both a DS-16M2 and DS-32M2 switch, the DS-16M2 should be positioned at the top of the rack/cabinet, located above the DS-32M2 switch. 12 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 13
    Installing the DS-16M and DS-32M Rails Select the appropriate length rails, and follow the steps below to install them. 1. Assemble the toward the rack/cabinet front. See the figure below. "Top" up and to the rack/cabinet front EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 13
  • Dell DS-32M2 | Installation Guide - Page 14
    Installing the DS-16M and DS-32M Rails 3. Adjust the length of the rail to fit between the channels in the rack/ -tight. Tighten them after the switch is installed. See the figures below. NOTE: The ball studs support the bezel. 14 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 15
    Installing the DS-16M and DS-32M Rails DS-32M Round-Hole Channel, Rack Front DS-32M Square-Hole Channel, Rack/Cabinet Front If you are installing the switch u-shaped flange of the rail with two holes in the rear inside channel. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 15
  • Dell DS-32M2 | Installation Guide - Page 16
    on page 3). Leave the screws finger-tight, and tighten them after the switch is installed. See the figure below. DS-32M Round-Hole Channel, Rear DS-32M Square-Hole Channel, Rear 9. Repeat steps 1 through 8 for the other rail. 16 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 17
    bracket orient correctly with the screw holes in the switch, first align the bracket's middle screw hole with the middle screw hole in the switch. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 17
  • Dell DS-32M2 | Installation Guide - Page 18
    Installing the DS-16M2 and DS-32M2 Switches ! CAUTION The kits include two (2) sets of screws. To avoid damaging the screw holes, be rack/cabinet. 4. Tighten the rear screws securing the rails to the rear of the rack/cabinet. 18 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 19
    Installing the DS-16M2 and DS-32M2 Switches 5. Push the switch further into the rack/cabinet until the hole in the front part of each with two M3 x 8 mm pan-head screws (see the table on page 3), one on each side, as shown below. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 19
  • Dell DS-32M2 | Installation Guide - Page 20
    a 39U rack. 10. Plug one of the supplied power cords into each of the switch's two power receptacles. 11. When installing the DS-16M2 switch, run the power cords up in front of the units and over the top of the uppermost switch. 20 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • Dell DS-32M2 | Installation Guide - Page 21
    enough room to loop the cord up without pushing the bezel off. 12. When installing the DS-32M2 switch, the 2U spacing allows you to run the power cords between the switches. 13. Secure end into available receptacles on the PDU. EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide 21
  • Dell DS-32M2 | Installation Guide - Page 22
    EMC2, EMC, CLARiiON, and Navisphere are registered trademarks and Access Logix, SnapView and MirrorView are trademarks of EMC Corporation. All other trademarks mentioned herein are the property of their respective owners. 22 EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22

1
This document explains the power, cooling, weight, and rack placement
requirements for the EMC departmental switches listed below. It also
describes the kits available for mounting them in EMC and non-EMC
racks and includes installation instructions as well.
Major sections are
Device Power, Cooling, and Weight Information
.................................
2
Device Dimensions
....................................................................................
2
Device Placement Requirements
.............................................................
2
Switch Mounting Kit (DS-16M or DS-32M)
...........................................
3
Installing the DS-16M and DS-32M Rails
...............................................
5
Installing the DS-16M2 and DS-32M2 Switches
..................................
17
EMC Departmental Switches
DS-16M2 and DS-32M2
Installation Guide
P/N 014003063
REV A02
August 1, 2002
Device
Device Model
Mounting Kit Model
16-Port Departmental Switch (2Gb)
DS-16M2-0D
DS16M-CRKH/CRKL
32-Port Departmental Switch (2Gb)
DS-32M2-0D
DS32M-CRKH/CRKL